506878-01
Page 49 of 62
Issue 1139
Proper Combustion
Furnace should operate minimum 15 minutes with correct
manifold pressure and gas flow rate before checking
combustion. Take combustion sample beyond the flue outlet
and compare to the tables below.
The maximum carbon
monoxide reading should not exceed 50 ppm.
Manifold Pressure Measurement
1. A manifold post located on the gas valve provides access
to the manifold pressure. See Figure 57. Back out the
3/32 Hex screw one turn, connect a piece of 5/16” tubing
and connect to a manometer to measure manifold
pressure.
2. Start unit and allow 5 minutes for unit to reach steady
state.
3. While waiting for the unit to stabilize, observe the flame.
Flame should be stable and should not lift from burner.
Natural gas should burn blue.
4. After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in Table
14.
NOTE:
Shut unit off and remove manometer as soon as an
accurate reading has been obtained. Take care to re-tighten
the 3/32 Hex screw.
Gas Pressure Adjustment
Gas Flow (Approximate)
Furnace should operate at least 5 minutes before checking
gas flow. Determine time in seconds for
two
revolutions of
gas through the meter. (Two revolutions assures a more
accurate time.)
Divide by two
and compare to time in
Table 12. If manifold pressure matches Table 14 and rate
is incorrect, check gas orifices for proper size and restriction.
Remove temporary gas meter if installed.
NOTE:
To obtain accurate reading, shut off all other gas
appliances connected to meter.
Supply Pressure Measurement
A threaded plug on the inlet side of the gas valve provides
access to the supply pressure tap. Remove the threaded
plug, install a field-provided barbed fitting and connect a
manometer to measure supply pressure. Replace the
threaded plug after measurements have been taken.
For proper furnace operation the minimum gas supply
pressure is 4.5" w.c and the maximum gas supply pressure
is 10.5" w.c for natural gas. The minimum gas supply
pressure is 10" w.c. and the maximum gas supply pressure
is 13" w.c. for LP/propane gas.
Table 13
Table 12
Table 14
Manifold and Supply Line Pressures Altitudes
Summary of Contents for 95G2UHV
Page 3: ...506878 01 Page 3 of 62 Issue 1139 EXPANDED VIEW Figure 1 ...
Page 28: ...506878 01 Page 28 of 62 Issue 1139 Figure 31 FIELD SUPPLIED WALL TERMINATION ...
Page 29: ...506878 01 Page 29 of 62 Issue 1139 Figure 32 ...
Page 35: ...506878 01 Page 35 of 62 Issue 1139 Figure 47 TRAP DRAIN ASSEMBLY USING 1 2 PVC or 3 4 PVC ...
Page 46: ...506878 01 Page 46 of 62 Issue 1139 TYPICAL WIRING DIAGRAM Figure 56 ...
Page 60: ...506878 01 Page 60 of 62 Issue 1139 Start Up Performance Check List UNIT SET UP ...
Page 61: ...506878 01 Page 61 of 62 Issue 1139 UNIT OPERATION Heating Mode Cooling Mode ...