Unit is operating and blows evaporator air but the supply air is not colder than the
return air from the cellar
Possible Cause
Solution
Remote interface controller not set up
properly
Compressor not operating
Condenser airflow is blocked
Check remote interface controller setup in
the manufactures guide
High pressure switch open (button up)
Alarm will appear on remote interface controller
Remove blockage
Clean filter and coil (if needed)
Head Pressure (HP) switch is open
Reset HP switch
See reset instructions on pg. 70
Cellar temperature too cold (below 51° (10°C) when unit is running
Possible Cause
Solution
Remote interface controller set too low
on cooling
Heating coil (optional) not operating
Remote interface controller set too low
on heating
Remote interface controller not controlling
temperature
Reset remote interface controller to
higher cooling temperature
Check for remote interface controller rise
across coil
Reset remote interface controller to
higher heating temperature
Remote interface controller mounted in
improper location
Cellar temperature too cold (below 51° (10°C) when unit is not running
Possible Cause
Solution
Too much heat loss to adjacent spaces
Cellar loads are too high
Increase insulation around the ductwork
Check and clean filter and coil
Coil frozen – shut off unit for two hours
Install additional insulation
Humidity too low or supply air is too cold, without optional humidifier
Possible Cause
Solution
Not enough evaporator airflow
Defective thermal expansion valve
Temperature set too cold
Remove blockage in supply or return ductwork
Check and clean filter and coil
Coil frozen – shut off unit for two hours
If under warranty call for service
If not under warranty call a refrigeration
technician
Raise temperature setpoint
Summary of Contents for 99H0360-10
Page 12: ...12 Xtreme Low Ambient Illustrations Fig 1 Fig 2 Pressure cutout timer 33c0185 00...
Page 14: ...14 Condensing unit dimensions DS050 COND NO OPTIONS...
Page 15: ...15 Refrigeration Illustration of the system See next page for magnified image...
Page 16: ...16 Magnified Image of the Condensing Unit...
Page 17: ...17 Wiring Diagram for DS025 DS050 WGS40 WGS75...
Page 18: ...18 Wiring Diagram for DS088 and WGS100...
Page 19: ...19 Wiring Diagram for DS200 and WGS175 Units...
Page 20: ...20 Wiring Diagram for Replacement Fan Motor XR 115 230 Models...
Page 21: ...21 Wiring Diagram for DS025 and WGS40 Condensing Unit...
Page 22: ...22 Wiring Diagram for DS050 and WGS75 Condensing Unit...
Page 23: ...23 Wiring Diagram for DS088 and WGS100 Condensing Unit...
Page 24: ...24 Wiring Diagram for DS200 and WGS175 Condensing Unit...
Page 25: ...25 Ducted Split Systems Specifications 60Hz Models DS025 DS050 DS088 DS200...
Page 26: ...26 Ducted Split System Specifications 50 Hz Models WGS40 WGS75 WGS100 WGS175...
Page 44: ...44 Install refrigeration piping per local codes and ASHRAE guidelines...