51
Examples of adjustments:
(Less than 25’/7.62 meters): If a WGS40 system that is only 15’/4.57 meters (10’/3.05 meters less
than factory charge baseline from table above) in total length. At .50oz/foot & .0465kg/meter
adjustment, that equals a decrease in total system charge from factory baseline of 5oz /.142kg.
Now a total system charge of 53oz/1.498kg. You then can subtract the initial factory charge of
16oz/.453kg from this new total, and that is the amount you ADD to the system upon start-up.
In this example = 37oz/1.045kg ADDED
(Greater than 25’/7.62 meters): If a WGS40 system that is 35’/10.67 meters (10’/3.05 meters
greater than factory charge baseline from table above) in total length. At .50oz/foot &
.0465kg/meter adjustment, that equals an increase in total system charge from factory baseline of
5oz /.142kg. Now a total system charge of 63oz/1.78kg. You then can subtract the initial factory
charge of 16oz/.453kg from this new total, and that is the amount you ADD to the system upon
start-up.
In this example = 47oz/1.327kg ADDED
Additional Charge for Xtreme Low Ambient Systems (XLA Option)
For systems that have Wine Guardian’s XLA option installed. Add the following additional charge to the system.
SS018, DS025, DS050
4.0 oz
WGS25, WGS40, WGS75
4.0 oz
DS088, DS200
6.0 oz
WGS100, WGS175
6.0 oz
Once the system has been charged compare the high side system pressure to the “discharge line pressure” found
on the “Split System Operations Chart” on page 50 for proper operation. If actual discharge pressures do not
match the chart then compare subcooling values as additional charge may be needed.
Split System Operations Chart
***
Operation data is based on typical wine cellar conditions of 57
°
F (14 Deg C)DB/49
°
FWB (55%RH)
DS025
OD Ambient (F)
Suction (psig)
Discharge (psig)
Suction
Superheat (F)
Sub-cooling (F)
10 ºF / -12 ºC
21
100
7 ºF / -14 ºC
23 ºF / -5 ºC
40 ºF / 4 ºC
24
104
13 ºF / -10 ºC
24 ºF / -4 ºC
60 ºF / 15 ºC
24
107
22 ºF / -5 ºC
20 ºF / -6 ºC
70 ºF / 21 ºC
24
108
25 ºF / -4 ºC
18 ºF / -7 ºC
80 ºF / 26 ºC
24
108
31 ºF / -1 ºC
16 ºF / -8 ºC
100 ºF / 37 ºC
27
150
38 ºF / 3 ºC
19 ºF / -7 ºC
115 ºF / 46 ºC
30
190
40 ºF / 4 ºC
21 ºF / -6 ºC
DS050
Summary of Contents for 99H0360-10
Page 12: ...12 Xtreme Low Ambient Illustrations Fig 1 Fig 2 Pressure cutout timer 33c0185 00...
Page 14: ...14 Condensing unit dimensions DS050 COND NO OPTIONS...
Page 15: ...15 Refrigeration Illustration of the system See next page for magnified image...
Page 16: ...16 Magnified Image of the Condensing Unit...
Page 17: ...17 Wiring Diagram for DS025 DS050 WGS40 WGS75...
Page 18: ...18 Wiring Diagram for DS088 and WGS100...
Page 19: ...19 Wiring Diagram for DS200 and WGS175 Units...
Page 20: ...20 Wiring Diagram for Replacement Fan Motor XR 115 230 Models...
Page 21: ...21 Wiring Diagram for DS025 and WGS40 Condensing Unit...
Page 22: ...22 Wiring Diagram for DS050 and WGS75 Condensing Unit...
Page 23: ...23 Wiring Diagram for DS088 and WGS100 Condensing Unit...
Page 24: ...24 Wiring Diagram for DS200 and WGS175 Condensing Unit...
Page 25: ...25 Ducted Split Systems Specifications 60Hz Models DS025 DS050 DS088 DS200...
Page 26: ...26 Ducted Split System Specifications 50 Hz Models WGS40 WGS75 WGS100 WGS175...
Page 44: ...44 Install refrigeration piping per local codes and ASHRAE guidelines...