
64
Fan AUTO or
ON
Setting 7
•
Press “Settings” button to advance to Setting
7.
•
Press the “Up” or “Down” arrow buttons to
adjust number to the desired set point. Factory
default is zero (0).
Zero (0) = Auto–fan only turns on when there
is a call for cooling or heating
One (1) = Fan On–fan remains on
continuously
Compressor
anti-short cycling
Setting 8
•
Press “Settings” button to advance to Setting
8.
•
Press the “Up” or “Down” arrow buttons to
adjust to the desired time in one-minute
increments. Maximum is 10 minutes,
minimum is 3 minutes. Factory default is 5
minutes.
Compressor anti-short cycling time is the
amount of allowable time between compressor
stop and restart. Rapid start/stop of
compressors can cause premature failure.
WINE GUARDIAN DOES NOT
RECOMMEND SETTINGS LOWER
THAN FACTORY DEFAULT.
Defrost sensor
enable/disable
Setting 9
•
Press “Settings” button to advance to Setting
9.
•
Press the “Up” or “Down” arrow buttons to
adjust to the desired setpoint.
1 will equal enabled and a 0 (zero) will equal
disabled.
Defrost cut-in
temperature
Setting 10
•
Press "Settings" button to advance to Setting
10.
•
Press the “Up” or “Down” arrow buttons to
adjust to the desired setpoint. This setting is
adjustable from 25°F to 40°F. Factory default
is 39°F.
There must be at least a 1°F difference
between defrost cut-in and cut-out set points.
Summary of Contents for 99H0360-10
Page 12: ...12 Xtreme Low Ambient Illustrations Fig 1 Fig 2 Pressure cutout timer 33c0185 00...
Page 14: ...14 Condensing unit dimensions DS050 COND NO OPTIONS...
Page 15: ...15 Refrigeration Illustration of the system See next page for magnified image...
Page 16: ...16 Magnified Image of the Condensing Unit...
Page 17: ...17 Wiring Diagram for DS025 DS050 WGS40 WGS75...
Page 18: ...18 Wiring Diagram for DS088 and WGS100...
Page 19: ...19 Wiring Diagram for DS200 and WGS175 Units...
Page 20: ...20 Wiring Diagram for Replacement Fan Motor XR 115 230 Models...
Page 21: ...21 Wiring Diagram for DS025 and WGS40 Condensing Unit...
Page 22: ...22 Wiring Diagram for DS050 and WGS75 Condensing Unit...
Page 23: ...23 Wiring Diagram for DS088 and WGS100 Condensing Unit...
Page 24: ...24 Wiring Diagram for DS200 and WGS175 Condensing Unit...
Page 25: ...25 Ducted Split Systems Specifications 60Hz Models DS025 DS050 DS088 DS200...
Page 26: ...26 Ducted Split System Specifications 50 Hz Models WGS40 WGS75 WGS100 WGS175...
Page 44: ...44 Install refrigeration piping per local codes and ASHRAE guidelines...