Installation-, Operating-, Maintenance-Manual, Spare Part List
BCR04
AGT-PSG GmbH & Co.KG
Errors and printing mistakes excepted
Page 19
Translation - Manual BCR04 Rev. 6/2017
Temperature-Monitoring and Error-Diagnosis
LED-Display
2.5
Pressure dew point display during operation. Blinking display at temperature alarm.
F1L/F1H
Error sensor-1: Sensor-mistake/short-circuit. Check/replace sensor-1.
.
EP
Data loss in parameter memory (rule-contacts are dead). Switch off the dryer and
restart it.
---
Button lock active.
NOTICE: Temperature display!
A dew point within 0°C and +10°C displayed on the control
unit is correct according to the possible working conditions (gas flow-rate, gas inlet
temperature, gas inlet dew point, ambient temperature, etc.). If the dew point goes under 0°C
or over +10°C a malfunction is reported over the potential free alarm contact.
CAUTION! Switching Celsius/Fahrenheit!
The display of temperatures can reconvert
between degrees Fahrenheit and degrees Celsius. Changing this parameter, the scheduled
values keep their number-area and the adjustment range. They need to become manually
adjusted.