Installation Planning
DD+DIS303.03E
Chapter 14 / 34
Classic E.O.S. / Classic E.O.S. CL
Edition 6, Revision 0
(Type 5270 / 100 / 105)
Radiation effects
Upon machine installation in the close vicinity to
the X-ray room, the local regulations for radiation
protection must be followed (protection of
personnel against scattered radiation). The
machine has not been designed for the
installation in the X-ray room, i.e. there is no
internal screening against scattered radiation.
Floor conditions
Waterproof, chemical-resistant floor covering
(pH value 4 - 11)
A floor drain close to the film processor is
recommended.
Floor load
50 N / cm² (7.75 N / in²)
A cleaning sink with water tap and hose shower
should be provided for maintenance work.
Minimum inside dimensions of the sink:
Cleaning sink
Width
Depth
Height
70 cm (27.56 inch)
40 cm (15.75 inch)
20 cm (7.87 inch)
Heat emission
(approx. values)
Standby
(max.)
into the room
250 W / 900 kJ/h
Film run
(max.)
into the connected
exhaust
1200 W / 4320 kJ/h
into the room
900 W / 3240 kJ/h
total
2100 W / 7560 kJ/h
Exhaust
connect.
Integrated exhaust in the dryer is a
standard feature.
During film cycle the exhaust runs at full
capacity. During standby mode the
exhaust can be set to half-capacity via
the service program.
9.3
Transport and storage conditions
Ambient
temperature
up to max. -25 °C for 72 h
(IEC 68-2-1 (Ab))
max. 55 °C for 96 h
(IEC 68-2-2 (Bb))
Relative humidity in the given temperature range
between 5% and 95%.