Installation Planning
DD+DIS303.03E
Chapter 14 / 24
Classic E.O.S. / Classic E.O.S. CL
Edition 6, Revision 0
(Type 5270 / 100 / 105)
8.6 Water
connection
Also see Chapter 3
Water consumption
Permanent replenishment:
max. 3 liters / min (101.45 fl.oz. / min).
The water supply rate per square meter of processed
film can be changed via code.
Water pressure
2 bar (200 kPa) to 6 bar (600 kPa)
Water temperature
min. 5 °C
pH value
6.5 to 8
Water conductivity
value
min. 3µS/cm
Reliable level detection in the water tank cannot be
guaranteed if this value is too low.
Regulations
The free water supply of the machine is in compliance with
the regulations of DIN 1988
/ EN 1717:2001 (technical
regulations for the installation of drinking water).
Shut-off valve
-
Clutch
not
included
in
shipment
Threaded fitting
Pressure reducer
(manometer),
for water pressure > 6 bar
Flexible safety
pressure hose
Solenoid valve
527314sm.cdr
23
0
3
2000
(78.7)
1
2
4
5
6
7
Dimensions in mm (inch)
Figure 24
Dirt filter
•
Position the safety pressure hose, mounted at the dirt filter, all the way to
the shut-off valve or pressure reducer.
Safety
pressure hose:
CM+9036260160
tested in compliance with DIN 57700 Part 600
2 m (78.74 inch) long
³/
4
" union nut
•
For safety we recommend to provide a floor drain close to the machine.