38
SE-Power FS STO-manual vers. 1.6 en.12.08.2015
6
Commissioning
Note
Danger in the event of loss of the safety function!
Lack of the safety function can result in serious, irreversible injuries, e.g. due to
uncontrolled movements of the connected actuators.
Operate the safety module only:
-
in a built-in condition and
-
when all safety measures have been implemented.
Validate the safety function to complete commissioning
Section 6.4
Incorrect wiring, use of an incorrect safety module or external components that
were not selected according to the safety category, result in loss of the safety
function.
Carry out a risk evaluation for your application and select the circuitry and components
accordingly.
Note the examples
Section 5.3
6.1
Before commissioning
Perform the following steps to prepare for commissioning:
1.
Ensure that the safety module is correctly mounted (see
Section
2.
Check the electrical installation (connecting cable, pin allocation, see
Section 5.2
). Are all
protective earth conductors connected?
6.2
DIP switch setting
DIP switches for activating and controlling the fieldbus configuration are located on the safety
module.
The functionality of the DIP switch is dependent of the fieldbus interface used.
Set the DIP switches as described in the documentation for the servo drives SE-
Power FS or the corresponding fieldbus-specific product manuals see