AES SOLAR Subscriber
25
AES P/N 40-3100S Rev. 3, 3/14/2023
•
Use the Solar Panel selection from the
Power From
dropdown
.
.
Note: Can only select Solar Option
Important!
When using this selection,
16.5 V AC
is the
primary
power source and the
battery
is the
secondary
power source
.
•
AC Report Delay:
AC Report Delay is active when
Suppress AC Fault
is set to
NO
. The report delay is the
time that must pass before the Model 3100S Subscriber will send an AC failure or AC restoral message. This
feature helps prevent mesh network congestion in an area where many Subscribers have an AC power outage
at the same time. Messages can be set to transmit in a staggered fashion using the Random time setting.
The combined AC fail detection time delay of 100 minutes plus the random
AC Report Delay
between 0
‒
60
minutes results in time that does not exceed 160 minutes.
AC power must be lost for 100 minutes in order to be detected as a failure. AC power must be restored for at
least 100 minutes in order to be detected as a restore. Once either is detected, a message is created by the
subscriber and is sent to the central station.
An AC report delay is selected based on both this parameter and the setting of AC fault report suppression in the
setting of
Suppress AC Fault Reporting
.
•
AC Report Delay
–
Available settings:
─
Random Delay
: A random time ranging from 0
‒
60 minutes after 100 minutes of AC power loss.
Enter
R
into the box.
─
Fixed
delay
: A specific time ranging from 1
‒
60 minutes after 100 minutes of AC power loss.
─
No
Delay
: Immediate transmission after 100 minutes of AC power loss. This is not recommended.
•
Locally Announce AC Fault:
Set
Locally Announce AC Fault
to
Yes
/
No
by clicking the
Locally Announce AC
Fault
switch.
•
Suppress AC Fault Reporting:
Set
AC Fault Reporting
to
Yes/No
by clicking the
AC Fault Reporting
switch.
•
Suppress Battery Fault Reporting:
Set
Battery Fault Reporting
to
Yes/No
by clicking the
Battery Fault
Reporting
switch.
•
Suppress Charger Fault Report:
Set
Suppress Charger Fault Report
to
Yes
/
No
by clicking the
Suppress
Charger Fault Report
switch.
When changes are complete, click
Save
Changes
.
•
Power from 24 V DC and Battery