19
AES P/N 40-3100S Rev. 3, 3/14/2023
Zone Programming
Zone Input Condition
Supervised
Bypass
Fire
Inverted Fire
2.2k ohm EOL resistor
circuit
N
ormal
Input Ignored
N
ormal
N
ormal
Open circuit
A
larm
Input Ignored
T
rouble
A
larm
Short/closed circuit
A
larm
Input Ignored
A
larm
T
rouble
Alarm Panel Siren Input Options for Zones 5 and 6
Inputs for zones 5 and 6 pertain to security alarm panel siren output. The alarm panel condition is detected by the
subscriber through the zone input and a message sent to the central monitoring station. The following types of
Siren
Alarm
input types can be programmed for zones 5 and 6:
•
Bypassed – zone input is ignored
•
Temporal/Pulse alarm pattern
•
Steady/Even alarm pattern
Connect the Alarm Panel Siren terminals to the SOLAR subscriber siren input terminals.
6.10
CONSECUTIVE AT EVENTS
Set
Consecutive AT Events
to
Yes
for verbose reporting of alarm and trouble messages. This means that alarms and
trouble will be sent continuously alarm-trouble-alarm-trouble. Set to
No
for non-verbose reporting, which means that an
alarm can be sent, then a trouble, but if an alarm happens again without a restoral, the alarm will not be sent.
6.11
INVERTED FIRE
Set
Inverted
Fire
to
Yes
for an
open
zone input to report as an
alarm
and
a short
on a zone input report as
trouble
.
Otherwise, the default setting of
No
which reports open on a zone input as trouble and a short on a zone input as an
alarm (if Fire Zones = Yes).
Note:
Set all
unused
zones to
Bypassed
. Do
not
install EOL resistors on
Bypassed
zones.
6.12
RESTORAL
Restoral messages are sent for the zone when the
Restoral
switch is set to
Yes
.