26
6.21 HOT WATER CONTROL MODE
WARNING:
modification and/or setting of these functions and these pa-
rameters must only be carried out by authorized personnel possessing the
necessary technical skills to install and service these units. Incorrect set-
tings may lead to malfunctioning or damage to the unit and the system! An
incorrect setting may lead to not reaching the set-point, prolonged times
or excessive absorption.
At the commissioning parameter setting page, by touching “Hot water control
mode”, it can be set to “Auto” or “Manual”.
When it is set to “Manual”,"Running Frequency Setting" can be set, and the user
could change the parameter to fix the frequency of the compressor in the "Hot wa-
ter" mode, otherwise, the unit will automatically run based on the original logic.
After that, this setting will be saved by touching the “Save” icon.
Hot water control mode
Hot water control mode: Manual
Running Frequency Setting: 50Hz
Note: If the relative function is activated (paragraph "8.1 Activating/deactivating
the memory (On/off memory) p. 32"), the value of these parameters will be stored
in the memory and automatically reset after any possible voltage failure.
6.22 SG FUNCTION (SMART GRID)
It is allowed to be activated only when the control panel is tu rned off. When it has
been activated, the operating main unit will receive and execute control commands
from the smart grid, except when the control panel has been turned off. See the
table below for the SG control commands.
SG (Smart Grid)
EVU (Photovoltaic signal)
Command
Note
1
0
Switch-off command
Stand-by command with “EVU”displayed at the control panel
0
0
Normal working
Switch-on command, the main unit operates freely
0
1
Switch-on signal
Switch-on signal (raise the target water temperature)
1
1
Switch-on command
Switch-on signal (raise the target water temperature to the highest)
6.23 COOL CONTROL MODE
When it has been activated, it will limit the highest frequency of the compressor for
cooling operation.
6.24 HEAT CONTROL MODE
When it has been activated, it will limit the highest frequency of the compressor for
heating operation.
6.25 HIGHEST WATER PUMP SPEED LIMIT FUNCTION
When it has been activated, there are three options for the highest speed of the wa-
ter pump, “High”, “Medium” and “Low”. “High” is for the speed level 10, “Medium” for
level 9 and “low” for level 8. Once it has been set, the operating speed of the water
pump is not allowed to exceed this set value.
6.26 WATER PUMP ANTISTALL
When it has been activated, it allows to set the antistall interval and antistall dura-
tion for the water pump. Once the main unit has been turned off, the water pump
will run at the highest speed for antistall duration every antistall interval so as to
prevent the water pump from being damaged.