12
4.7 WEEKLY TIMER
At the function setting page, by touching “Weekly timer”, it will go to the setting
page as shown below.
After accessing the “Weekly timer” function, you can set up to three time bands for
each single day of the week; during these time bands, the unit will work with the
current mode and set-point. Alternatively, you can assign the “Holiday” value to one
day or more; if the specific “Holiday program“ function is enabled, an operating set-
point of 30°C will be automatically set if you use the check on the delivery water,
or 10°C if you use the ambient air check (installing the specific air probe accessory).
Weekly timer
Weekly timer: On
Mon: Valid
Tue: Invalid
Wed: Invalid
Thur: Invalid
Fri: Invalid
Sat: Holiday
Sun: Holiday
At the “Weekly timer” setting page, as shown in the figure above, the weekly timer
can be set to “On” or “Off”.
At the “Weekly timer” setting page, by touching the desired day (Monday~Sunday)
it will access to the setting page of this option.
At the weekday setting page, it is able to set the timer to “Valid” or “Invalid”. Also,
it is able to set three timing periods, each of which can be set to “Valid” or “Invalid”.
Then, by touching the “Save” icon, this setting will be saved.
00 00
01 01
02 02
23 59
22 58
Period 1
Period 1: Valid
Start Timer: 00:00
End Timer: 00:00
Note:
— You can set up to three time bands (periods) for each day; their start and end
times must be coherent (the start of one period must be later than the end of
the previous one);
— When the weekly timer has been activated, the display panel will act based on
the current mode and temperature setting;
— The “With” setting for one or more days of the week validates the specified time
settings only if the Weekly Timer is “On”;
— “Without” = the Weekly Timer is also active, this day will not be considered;
— When both “Weekly timer” and “Holiday release” have been activated, setting of
“Weekly timer” is invalid.
— The priority sequence for timer setting from high to low is “Temperature tim-
er”, “Clock timer”, “Preset mode” and “Weekly timer”. Setting with lower priority
sequence is allowed but does not work when setting with higher priority has
been activated. However, it will work when the setting with higher priority has
been deactivated.
— If the relative function is activated (paragraph "8.1 Activating/deactivating the
memory (On/off memory) p. 32"), the value of this parameter will be stored in
the memory and automatically reset after any possible voltage failure.
4.8 HOLIDAY RELEASE
Holiday release
On
Off
OK
Cancel
After accessing the “Holiday release” function, you can enable or disable this pro-
gram if applied as a daily setting on one or more days of the weekly timer. Select
the setting, then press “OK” to confirm.
Note:
— If one day or more is set on “Holiday” in the weekly timer, this function must be
“On” if you want the program specified in the timer to be respected;
— If the relative function is activated (paragraph "8.1 Activating/deactivating the
memory (On/off memory) p. 32"), the value of this parameter will be stored in
the memory and automatically reset after any possible voltage failure.
4.9 DISINFECTION
After accessing the “Disinfection” function, you can enable or disable this function,
as well as choose the time and day to run it and the temperature to be used:
Disinfection
Disinfection: Off
Set clock: 23:00
Set temp.: 70°C
Set day: Mon.
00 00
01 01
02 02
23 59
22 58
Then, by touching the “Save” icon, this setting will be saved.
Note:
— If the compatible Aermec accessory tank for this model (refer to the installation
manual for more information) is not installed and correctly set, this function will
not be available;
— This function can only be activated if the unit is switched off;
— This function cannot be activated simultaneously with: “Emergen. mode”, “Holi-
day mode“, “Floor debug“, “Manual defrost“, “Refri. recovery“;
— If the anti-legionella cycle is not completed, the unit will produce a message on
the screen to indicate the anomaly. This message can be reset by pressing “OK”;
— An anti-legionella cycle will automatically be interrupted by any possible com-
munication error or an error linked to the storage tank accessory;
— If the relative function is activated (paragraph "8.1 Activating/deactivating the
memory (On/off memory) p. 32"), the value of this parameter will be stored in
the memory and automatically reset after any possible voltage failure.
WARNING:
if the unit is used to produce domestic hot water, the Anti-Le-
gionella Cycle MUST be set. The ANTI-LEGIONELLA CYCLE is related to only
the mandatory tank accessory. To ensure a reduction in and control of the
legionella risk, the preventive measures indicated in the guidelines, regula-
tions and local rules must be adopted.