4.13    HOLIDAY  MODE

At the function setting page, select “Holiday mode” and set it to “On” or “Off”.
You can use the weekly timer to assign the “Holiday” program to at least one day 
of the week. On those days, the unit will work in heating mode, maintaining a 30°C 
set-point on delivery water (or 10°C if the check is based on the ambient air). To 
enable the implementation of the Holiday Program (if set on the weekly timer), you 
must activate this function.
After accessing the “Holiday mode” function, you can choose one of the modes 
available by clicking directly on the text that identifies it and then confirming with 
the ”OK” key.

Holiday mode

On

Off

OK

Cancel

 

Note:

—  Before changing the operating mode, the unit must be OFF, otherwise a mes-

sage will warn you to turn the unit off before changing the mode;

—  During the use of Holiday mode (as set in the weekly timer), the operating 

mode will be automatically set on “Heating” and the On/Off command from the 
panel cannot be used;

—  None of the functions linked to the timers will be available during Holiday 

mode;

—  You can use the weekly timer to assign the “Holiday” program to at least one day 

of the week. On those days, the unit will work in heating mode, maintaining a 
30°C set-point on delivery water (or 10°C if the check is based on the ambient 
air). To enable the implementation of the Holiday Program (if set on the weekly 
timer), you must activate this function.

—  Certain functions are not available in Emergency mode so, if you attempt to 

activate them, the system will tell you to disable Emergency mode first;

—  If the relative function is activated (paragraph "8.1 Activating/deactivating the 

memory (On/off memory) p. 32"), the value of this parameter will be stored in 
the memory and automatically reset after any possible voltage failure.

4.14    PRESET  MODE

At the function setting page, select “Preset mode” and go to the corresponding set-
ting page.
This function is used to set one to four daily periods, whose commands will then 
be executed every day. After accessing the “Preset mode” function, you can press 
the key for each period to activate or deactivate an individual period, choose the 
operating mode to be used, the temperature set-point for processed water, and the 
start and end times of the period itself.

Preset mode

Period 1: Valid

Period 2: Invalid

Period 3: Invalid

Period 4: Invalid

At the time period setting page, each time period can be set to “Valid” or “Invalid”.

Preset mode

Period 1: Valid

Mode: Heat

WOT Heat: 45°C

Start timer: 00:00

End timer: 00:00

Clicking on the "Period" label will open the page with the labels relating to period 
activation, the mode to be used during the period, the water delivery temperature 
and the start and end times. Click on each of these to set the appropriate value 
(each data item may draw up additional windows for selecting or entering the re-
quired values). Lastly, press the top right button to save the data entered.

 

Note:

—  If the compatible Aermec accessory tank for this model (refer to the installation 

manual for more information) is not installed and correctly set, the “DHW” func-
tion will not be available;

—  If timer programming with the Weekly timer and other settings with Preset 

mode have been entered simultaneously, the latter will take priority;

—  When the water tank is available, the preset mode can be "Heat", "Cool", or "Hot 

Water"; however, when the water tank is unavailable, the preset mode can only 
be "Heat" or "Cool".

—  Up to four time bands can be set for each day, but their start and end times 

must coherent (the beginning of one period must be later than the end of the 
previous period);

—  If the unit is switched on manually, the period timer programs will not be im-

plemented;

—  When "Start timer" is reached, the unit will perform the preset mode. When 

"End timer" is reached, the unit will perform OFF operation.

—  If the relative function is activated (paragraph "8.1 Activating/deactivating the 

memory (On/off memory) p. 32"), the value of this parameter will be stored in 
the memory and automatically reset after any possible voltage failure;

—  When "Weather depend" has been activated and the mode for "Preset mode" 

is set to "Hot water", "Weather depend" will be deactivated when the setting 
mode has been switched.

Summary of Contents for HMI-1

Page 1: ...2 3 0 5 6 2 2 8 1 4 1 _ 0 0 T r a n s l a t i o n o f O r i g i n a l i n s t r u c t i o n s User manual w w w a e r m e c c o m 2020 02 20 08 52 0 0 C 0 0 C 25 C HMI_1 WIRED CONTROLLER ...

Page 2: ... any notice thereof Thank you again Aermec S p A COMPANYCERTIFICATIONS SAFETYCERTIFICATIONS This marking indicates that this product should not be disposed with other household wastes throughout the EU To prevent possible harm to the envi ronment or human health from uncontrolled disposal of Waste Electrical and Electronic Equipment WEEE please return the device using appropriate collection system...

Page 3: ...heat source Other thermal p 21 Setting an additional heater Optional E heater p 22 Setting the installation of the remote room temperature probe Ambient sensor p 22 Air removal p 22 Setting the pre heating procedure for radiant panels Floor debug p 23 Manual defrosting p 24 Force mode p 24 Activating auxiliary device management Gate Ctrl p 24 Setting of max absorption A P limit p 24 Setting the se...

Page 4: ...4 Setting the system date and time Time Date p 32 Activating the WiFi WiFi p 32 ModBus RS485 connection p 33 ...

Page 5: ... Ensure to be able to use the correct communication ports otherwise the connection may not work properly Never beat throw and frequently disassemble the wired controller and the wireless remote controller Never operate the wired controller and the wireless remote controller with wet hands Do not remove or install the wired controller by yourself If there is any question please contact our after sa...

Page 6: ...e room temperature This icon indicates that an alarm is currently in progress This icon may indicate External contact Anti legionella cycle failed This icon indicates that the panel is locked The main unit keeps the standby status under the SG control command while several keys are available at the bottom of the display Button Function Key to return to the menu selection window Key to change the o...

Page 7: ...oning parameter setting page 8 ON OFF It used to turn on or off the unit OFF indicates the unit has turned off and ON indicates the unit has turned on Where there is failure level error this button will turn to OFF once the unit is automatically turned off 9 General Allows to go to the general parameter settings page 10 Home Page Back to the home page Icon Meaning Icon Meaning Heating Floor commis...

Page 8: ... or off through another window where the on off command can be confirmed or cancelled Note 1 Once the voltage supply has been connected for the first start up this function will be set on Off 2 ON OFF operation will be memorized by setting On Off Memory to be On at the General menu That is in case of power failure the unit will resume running upon power recovery Once On Off Memory is set to be Off...

Page 9: ... Note 1 1 Mode Cooling Heating When the water tank is unavailable then only Cool and Heat are avail able Heating Hot domestic water Cooling hot water Heating DHW 2 Fast hot water On Off Off When the water tank is unavailable it will be reserved 3 Cooling hot water Cool hot water D H W When the water tank is available it will be defaulted to be Hot water when unavailable it will be reserved 4 Heati...

Page 10: ...r Cool OK Cancel At the function setting page with the unit turned off by touching Cool hot wa ter the display panel will go to the corresponding setting page where desired op tion can be selected Then by pressing OK this setting will be saved and the display panel will back to the function setting page After accessing the Cool hot water function you can select Cool to force the unit to first of a...

Page 11: ...her depend function you can set all the parameters re lated to offsetting work set points in accordance with variations in outside air tem perature To activate this function click on the Weather depend label the first item on the first page of the function Select On and then confirm with OK Weather depend On Off OK Cancel Subsequently the values for the various parameters that make up climatic cur...

Page 12: ...tion is activated paragraph 8 1 Activating deactivating the memory On off memory p 32 the value of this parameter will be stored in the memory and automatically reset after any possible voltage failure 4 8 HOLIDAY RELEASE Holiday release On Off OK Cancel After accessing the Holiday release function you can enable or disable this pro gram if applied as a daily setting on one or more days of the wee...

Page 13: ...t the same time the weekly timer takes priority When the water tank is available Heat Cool Hot Heat Hot water and Cool Hot water are allowed however when the water tank is unavailable only Heat and Cool are allowed The timer start must always be prior to the timer end otherwise the period will not be valid Water tank temperature can be set only when Hot water is involved in the op eration mode The...

Page 14: ...he electric heater of the storage tank and or the additional heat source or electric heater to meet the re quests After accessing the Emergen mode function you can enable or disable this program you must then press OK to confirm 1 At the function setting page set the mode to Heat or Hot water 2 At the function setting page select Emergen mode and set it to On or Off 3 When Emergen mode has activat...

Page 15: ... After accessing the Preset mode function you can press the key for each period to activate or deactivate an individual period choose the operating mode to be used the temperature set point for processed water and the start and end times of the period itself Preset mode Period 1 Valid Period 2 Invalid Period 3 Invalid Period 4 Invalid At the time period setting page each time period can be set to ...

Page 16: ...ns to the home page and the icon is shown in the upper part of the display 2020 02 20 08 52 0 0 C 0 0 C 25 C In this case the panel is locked and cannot respond to any commands To unlock the panel press the icon for 6 seconds however the child lock function is still set to on and if no other operations are performed within 30 sec onds the panel locks again It is only actually disabled when set to ...

Page 17: ...ΔT hot water 2 25 C 5 C 9 Room temperature control difference Δt4 ΔT room temp 1 5 C 2 C 10 Temperature difference between actual and target water for cooling ΔWT Cool AT 10 0 C 5 C 11 Temperature difference between actual and target water for heating ΔWT Heat AT 0 15 C 5 C 12 Temperature difference between actual and target water for water heating ΔWT hot water AT 0 15 C 5 C 13 Minimal allowable ...

Page 18: ...set and or mod ified by authorised personnel with the necessary technical skills to install and maintain these units Incorrect settings may lead to malfunctioning or damage to the unit and the system Commissioning Function Setting Number Displayed name Range Default Note 1 Ctrl state T water out T room T water out When Remote sensor is set to With it can be set to T room 2 2 Way valve Cool 2 Way v...

Page 19: ...ctivating deactivating the memory On off memory p 32 the value of these parameters will be stored in the memory and automatically reset after any possible voltage failure 6 2 SETTING THE STATUS OF THE 2 WAY VALVE IN COOLING MODE COOL 2 WAY VALVE Cool 2 way valve On Off OK Cancel After accessing the Cool 2 Way valve function you can set the status of the 2 way valve in cooling mode for more informa...

Page 20: ...tion is active the external thermo stat cannot be used When Thermostat is active Temp timer function will be deactivated au tomatically and the unit will run based on the mode set by the thermostat Meanwhile mode setting and On Off operation by the control panel will be ineffective When Thermostat is set to Air the unit will run based on the setting of the thermostat If the external thermostat is ...

Page 21: ...al heat source will be activated once the set value has been reached the additional heat source will be deacti vated and the unit will activate its circulator DHW the unit and its circulator will not be active the 3 way valve will be blocked on the DHW side and the additional heat source will be activated Heating DHW 1 If the priority is Heating paragraph 4 4 Heating DHW p 10 the unit and its circ...

Page 22: ...ter cannot be started at the same time Logic 2 the heat pump and the optional electric heater can be started at the same time when the ambient temperature is lower than T Eheater The electric heaters for the system and the electric heater in the DHW tank available as an Aermec accessory will never be activated simultaneously If the relative function is activated paragraph 8 1 Activating deactivati...

Page 23: ...uration of each segment Segment time 12 72 hours 0 12 hours 5 Temperature difference of each segment ΔT of segment 2 10 C 5 C 1 C At the end press the button at the top right to start or interrupt the pre heating cycle Note This function can be activated only when the unit is turned off When it is done with the unit keeping On a warning will appear telling you to turn off the unit first When this ...

Page 24: ...will access to the corresponding setting page Gate Ctrl On Off OK Cancel After accessing the Gate Ctrl function you can activate or deactivate the manage ment of the switch on switch off command via the external contact for more in formation about this contact refer to the installation manual Make your selection then press OK to confirm Note When Gate Ctrl has been activated the display panel will...

Page 25: ...compressor and the electric heater in the tank cannot work simultaneously Logic 2 the unit compressor and the electric heater in the tank can work si multaneously Note If the compatible Aermec accessory tank is not installed this function will not be available To change the thermostat settings the unit must be switched Off If the relative function is activated paragraph 8 1 Activating deactivating...

Page 26: ...been activated the operating main unit will receive and execute control commands from the smart grid except when the control panel has been turned off See the table below for the SG control commands SG Smart Grid EVU Photovoltaic signal Command Note 1 0 Switch off command Stand by command with EVU displayed at the control panel 0 0 Normal working Switch on command the main unit operates freely 0 1...

Page 27: ...value within the per mitted range once the value has been set press the OK button to confirm it and return to the upper level Commissioning Parameters Setting Number Name Displayed name Range Default Note 1 T HP max T HP max 40 55 C 50 C Note For parameters with different defaults at different conditions once the current condition changes the corresponding default also will change If the relative ...

Page 28: ...m On Off Crankc heater Indicates the status of the compressor casing heater On Off HP heater 1 Indicates the status for stage 1 of the optional electric heater if installed paragraph 6 8 Setting an additional heater Optional E heater p 22 On Off HP heater 2 Indicates the status for stage 2 of the optional electric heater if installed paragraph 6 8 Setting an additional heater Optional E heater p 2...

Page 29: ... the water leaving the optional heater paragraph 6 8 Setting an additional heater Optional E heater p 22 T tank ctrl Indicates the temperature measured in the compatible Aermec accessory tank T economizer in Indicates the temperature on the economiser inlet T economizer out Indicates the temperature on the economiser outlet T floor debug Indicates the set temperature for radiant floor debug paragr...

Page 30: ...fault on the IPM module inverter power module Hc PFC defective Indicates an operating fault on the PFC module power correction module Lc Start failure Indicates a fault in the unit s start up phase Ld Phase loss Indicates a problem associated with the loss or unbalance of voltage phases P0 Driver reset Indicates a reset made on the unit s drivers P5 Com over cur Indicates that an overcurrent on th...

Page 31: ...h a bar chart 2023 10 000 7 500 2 500 5000 0 Last year Note Unit kWh Statistic data just for reference Total P C 39732 Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec 2022 10 000 7 500 2 500 5000 0 This year Note Unit kWh Statistic data just for reference Total P C 39732 Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Click the current month and then go to the daily power consumpt ion page as show...

Page 32: ... On off memory label to activate or deactivate the saving of parame ter function settings NOTE if this option is activated after a power failure the unit will automatically resume the values set and saved in the memory 8 2 SETTING THE SYSTEM DATE AND TIME TIME DATE At the GENERAL menu by touching Time Data it will go to the setting page as shown in the figure below 28 29 30 27 26 05 06 07 04 03 20...

Page 33: ...com qrcode asp q 15589 German http www aermec com qrcode asp q 15590 Spanish http www aermec com qrcode asp q 15591 8 4 MODBUS RS485 CONNECTION If you want to manage the unit via a BMS connected via ModBus RS485 refer to the information available in the dedicated manual available at the following address http www aermec com qrcode asp q 14459 ...

Page 34: ......

Page 35: ......

Page 36: ...V i a R o m a 9 9 6 3 7 0 4 0 B e v i l a c q u a V R I t a l i a T e l 3 9 0 4 4 2 6 3 3 1 1 1 F a x 3 9 0 4 4 2 9 3 5 7 7 m a r k e t i n g a e r m e c c o m w w w a e r m e c c o m http www aermec com qrcode asp q 19790 http www aermec com qrcode asp q 19789 http www aermec com qrcode asp q 19787 http www aermec com qrcode asp q 19788 http www aermec com qrcode asp q 19786 ...

Reviews: