Innovation Water Heaters Installation, Operation & Maintenance Manual
APPENDIX A – INNOVATION MENU ITEM DESCRIPTIONS
Page
138
of
206
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0078_0L
PRI: 11/25/2014
Phone: 800-526-0288
GF-128
Table A-4:
TUNING MENU ITEM DESCRIPTIONS
See section 3-7 for a range of choices and the default values.
MENU LEVEL & OPTION
DESCRIPTION
24
Temp Gov Enable
Enables or Disables the Temperature Governor function. The
Temperature Governor aggressively reduces the effective Fire
Rate as the Outlet Temperature approaches the High
Temperature Limit.
25
GOV Limit-5
When the Outlet Temperature exceeds the HIGH
TEMPERATURE LIMIT -5, the effective Fire Rate will be
reduced by the value entered in “GOV Limit -5”
26
GOV Limit-7
When the Outlet Temperature exceeds the HIGH
TEMPERATURE LIMIT -7, the effective Fire Rate will be
reduced by the value entered in “GOV Limit -7”
27
GOV Limit-10
When the Outlet Temperature exceeds the HIGH
TEMPERATURE LIMIT -10, the effective Fire Rate will be
reduced by the value entered in “GOV Limit -10”
28
GOV Limit-12
When the Outlet Temperature exceeds the HIGH
TEMPERATURE LIMIT -12, the effective Fire Rate will be
reduced by the value entered in “GOV Limit -12”
29
GOV Limit-15
When the Outlet Temperature exceeds the HIGH
TEMPERATURE LIMIT -15, the effective Fire Rate will be
reduced by the value entered in “GOV Limit -15”
30
PID Output
Calculated PID Output
31
P Output
Proportional Band Output
32
I Output
Integral Output
33
D Output
Derivative Output
34
Reset Defaults?
Allows Tuning Menu options to be reset to their Factory Default
values.
35
Value Debug
For Factory Personnel ONLY
36
Above 70 Fuel
For Factory Personnel ONLY
37
Below 70 Fuel
For Factory Personnel ONLY
NOTE:
Feedback Gain (Item 8) is only displayed when Heater Tuning Display is enabled by
factory authorized personnel.