Innovation Water Heaters Installation, Operation & Maintenance Manual
CHAPTER 6 – MAINTENANCE
Page
94
of
206
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0078_0L
PRI: 11/25/2014
Phone: 800-526-0288
GF-128
LWCO Capacitor Electrical Short Test
– Continued
2. Remove the Shell Harness Cable (male) connector from the P-5 (female) connector on the
rear panel of the C-More controller (see Figure 6-13).
Figure 6-13: Removing Shell Harness Cable from P5 Conn. on C-More Rear Panel
3. Using an ohmmeter, connect one ohmmeter probe to the LWCO capacitor terminal on the
unit shell as shown on left in Figure 6-14.
4. Connect the second ohmmeter probe to Pin #6 of Shell Harness Connector (removed
from the C-More controller) as shown on right in Figure 6-14.
Figure 6-14: Connecting Ohmmeter between LWCO Probe & Shell Harness Cable
Unplug Shell
Harness Cable
from
P5 Connector
Connect 1
st
Lead to LWCO
Connect 2
nd
Lead to PIN #6
19-Pin Shell Harness Cable
Connector
LWCO Probe Assembly
Ohmmeter