AMR Integrated Water Heaters (Supplement to GF-146)
CHAPTER 3: INSTALLATION - SITE
CHAPTER 3:
INSTALLATION - SITE
3.1 Choosing the Installation Location
This section describes the general installation considerations for the AM Series units.
WARNING!
Provisions for combustion air and ventilation of the water heater
room are always required, regardless whether the combustion air
is taken from the outside (Direct Vent, sealed combustion) or
inside (room air for combustion). Insufficient ventilation of the
water heater room can lead to high air temperatures. Make sure
that intake and exhaust openings are sufficiently sized and no
reduction or closure of openings takes place. If these are not
provided, do not operate the water heater.
WARNING!
LIQUEFIED PETROLEUM (L.P.) PROPANE GAS-FIRED
WATER HEATER
LOCATION REQUIRES SPECIAL
ATTENTION:
1994 UNIFORM MECHANICAL CODE, section
304.6: “LPG Appliances. Liquefied petroleum gas-burning
appliances shall not be installed in a pit, basement or similar
location where heavier-than-air-gas might collect. Appliances so
fueled shall not be installed in an above grade under-floor space
or basement unless such location is provided with an approved
means for removal of unburned gas.”
This appliance is not designed for direct outdoor installation. If installed outside of the structure,
it must be sheltered so it is protected from rain, wind, sun and frost. NEVER place this appliance
in a location that would subject it to temperatures at or near freezing or temperature that exceed
100°F (38°C). Failure to properly locate this unit can result in premature failure.
The unit must NOT be installed on carpeting.
This appliance must be installed in a location so that any water leaking from the unit or piping
connections or relief valve openings will not cause damage to the area surrounding the unit or
any lower floors in the structure. When such locations cannot be avoided, it is recommended
that a suitable drain pan, adequately drained, be installed under the water heater. The pan must
not restrict combustion air flow.
When installed in a room with thin flooring, resonating noises may occur. Install noise reducing
parts if required.
Do not allow excessive dust to collect on the appliance.
OMM-0106_0A
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
13
of
52
GF-146-IR
Ph.: 800-526-0288
PRI - 07/22/15