33
4.2.4 AC Current Measurement
Measurement
Range
0.15 to 59.99A
60.0 to 599.9A
600A
(1)
Specified
Measurement
Range
(2)
0 to 100% of the measurement range
Accuracy
± (1% R + 10cts)
± (1% R +3cts)
Resolution
0.01A
0.1A
1A
Note (1) Bandwidth in AC = 3kHz
Note (2) In AC, any value between zero and the min. threshold of the
measurement range (0.15A) is forced to show “----“ on the display.
Residual current at zero <150mA.
Specific Specifications in MAX/MIN mode
(from 10Hz to 1kHz, and from
0.30A in AC):
•
Accuracy (with zero corrected): add 1% R to the values of the table
above.
•
Capture of the extreme: approximately 100ms.
4.2.5 True Inrush
®
Measurement
Measurement Range
6 to 600A
AC
6 to 900A
DC
Specified Measurement Range
0 to 100% of the measurement range
Accuracy
± (5% R + 5cts)
Resolution
1A
Specific Specifications in PEAK mode in True InRush
®
(from 10Hz to 1kHz):
•
Accuracy: add ± (1.5% R +0.5A) to the values in the table above.
•
PEAK capture time: 1ms min. to 1.5ms max.
4.2.6 Continuity Measurement
Measurement Range
0.0 to 599.9
Ω
Open-circuit Voltage
≤
3.6V
Measurement Current
550µA
Accuracy
± (1% R +5cts)
Buzzer Triggering Threshold
Adjustable from 1 to 599
Ω
(40
Ω
is the default)