22
HA-263D (START THE PROGRAMMING)
HA-263
!
!
!
!
!
!
!
!
Each code can be selected for 1 or 0
1 = Beep Enabled (Default)
0 = Beep Disabled
The above beep settings are for the keypad only. They have nothing concern with the beep
settings on the main circuit board. The beeps for keypad and circuit board are independent.
The warning beeps for Battery Low and AC Power Failure cannot be OFF and is not affected
by the above settings.
The confirmation beeps from the
# keys are always enabled.
LOCATION
RESPONES TIME
VALIDATION
15
3 3 3 3 3 3 3 3
#
1 2 3 4 5 6 7 8
ZONES
The zone response time is fixed on 500mS for HA-263K, which is the value suitable for most of
the sensors' alarm output.
In some application environment or the nature of some sensors, shorter or longer response
time may be required for a protection zone. Please consult the sensor suppliers before setting
the time to the protection zone.
HA-263D allows the owner to set different response time to each protection zone
independently.
The 8 digit code represents the 8 protection zones. The first digit is zone 1 and the last digit is
zone 8. Owner can put the timing code into the specific digit to independently set the desired
response time for the 8 protection zones.
1 = 25mS
2 = 250mS
3 = 500mS (Default)
4 = 750mS
SET THE RESPONSE TIME TO DETECT AN ALARM FOR EACH ZONE
(Location 15)
RESPONSE TIME
The Timing Codes for Response Times
" " & " "
7:
8, 9, :
8:
9:
10:
11:
12:
This terminal pr12V output power at alarm condition with the time period
according to the setting of the alarm timer. It is suitable for energizing electronic siren or
alarm bell. The output is equipped with a 2.5A resettable fuse.
This group of terminals are the connection points for the digital keypads (HA-263D). All
keypads can be connected in a parallel configuration back to these terminals and more
than one keypads can be allowed. The maximum allowed number of keypads and
keyswitches are 4.
Common ground (-)
Clock wire
Data wire
+12V power common point, equipped with a 750mA resettable fuse
No connection to these terminals are required for HA-263K
This terminal is prepared for connection of keyswitches (RKS-2M) for arm-disarm control of
the Partition 1. It accepts Normally Open (N.O.) momentary type switches and is +12V
triggered. More than one switches can be connected in parallel.
NOTE:
13:
This terminal is prepared for connection of keyswitches (RKS-2M) for arm-disarm control of
the Partition 2. It accepts Normally Open (N.O.) momentary type switches and is +12V
triggered. More than one switches can be connected in parallel.
a) Terminal 12 and 13 can be connected together to one keyswitch for combined
arm-disarm control of the two partitions.
b) Hold the keyswitch in contact for more than 1/2 second to arm or disarm
Partition 1 or Partition 2. Two beeps will be generated to indicate that the
system is ready to arm.
c) If continuously hold any one of the keyswitch in contact for more than 5
seconds and ignore the 2 arming beeps will set system in Standby Mode.
NOTE:
UTILIZE THE KEY SWITCH FOR SYSTEM ARM-DISARM CONTROLS
7
CONNECTION TERMINALS
4
HA-263
10,11
ARM THE SYSTEM
DISARM THE SYSTEM
KEY SWITCH
CONTACT
One Touch
(>1/2 second)
1st Touch
(>1/2 second)
2nd Touch
(>1/2 second)
STATUS
!
!
!
Make arming for
partition 1 or 2
Make disarming for
partition 1 or 2
Alarm memory is
cleared & the
system keeps in
disarmed mode
RESULTS
!
!
!
!
!
!
!
Exit delay starts
Exit beep sounds if it is enabled
System will be armed after exit
delay expired
The system is disarmed and reset if
there was no alarm occurred. It is
ready for re-arming
The system is disarmed but with
alarm memory if there was alarm
occurred, 2nd touch is required
The alarm memory LEDs are off
The system is ready for re-arming
(both the STATUS LED on keyswitch
and the zone LEDs on the keypad)