CONNECTION TERMINALS

1 - 2 : 12 - 24V AC/DC (Power Input Terminal)

Connect to 12-24V AC or DC power supply. The (-) supply and (-) GND (terminals 2 & 12) are the 

common grounding points of the keypad system. No selection jumper is required for the full input 

voltage range. Connect DC power with the (+) and (-) polarity indicated; and there is no polarity 

discrimination for AC power input.

3 - 4 - 5 : OUTPUT 1 (Output Relay 1)

5 Amp relay dry contact controlled by the Group 1 User Codes/Cards, recommended for door strike. 

Terminal 3 is Normally Closed (N.C.), terminal 5 is Normally Open (N.O.) and terminal 4 is the 

common point of the two contacts. Use N.C. output for Fail-safe locking device; and N.O. output for 

Fail-secure locking device. The relay is programmable for Start/Stop (toggle) mode or Momentary 

timing mode. See programming Location 51 for the details.

6 - 7 - 8: OUTPUT 2 (Output Relay 2)

1 Amp relay dry contact with N.C. and N.O. outputs. Terminal 6 is the N.C.(Normally Closed). terminal 

8 is N.O. (Normally Open) and terminal 7 is the common point of the two contacts, which is prepared 

for actuating auxiliary device controlled by the keypad; or external door chime actuation controlled 

by the bell button. The  maximum rating of the relay contacts is 24 VDC/1A. 

DK-2852C - Standard Version

The Output relay 2 in DK-2852C is controlled by the Group 2 User Codes and Cards. It is 

programmable for Start/Stop (toggle) mode or Momentary Timer mode. See programming Location 

52 for the details.

DK-2852D - Door Bell Button Version

The Output relay 2 in DK-2852D is controlled by the door bell button on the keyboard. It is an output 

point for actuation of a low voltage external (optional) door chime. The contact point activates as 

long as the bell button is pressed



BACK-LIT JUMPER

CONNECTION 
TERMINALS

3) Split-decoded Access Control Door Lock

Description

Apart from stand-alone operation, the DK-2852 can be up-graded to high security Split-decoded 

operation with a decoder unit DA-2800 or DA-2801. The decoder is inside the house with all the 

input and output installations connecting to it. The DK-2852 manages the data in the system 

with its Data I/O Bus. The decoder operates the door lock and the appliances directly according 

to the commands from the keypad unit. This approach prevents the electric door lock or 

appliance be operated due to sabotage at the external keypad.

Note:

 Make 

Operation Mode

 setting of the keypad in 

“Server Mode”

 with 

Location 94 = 1

 in  

Wiring Diagram

System Connection

DK-2852 (SERVER)

(–) COMMON GND

(+) POWER SUPPLY

DATA I/O BUS

DK-2852

(SERVER)

DA-2800  OR 

DA-2801

(DECODER)

ELECTRIC LOCK

-
 ALA

RM O/P

-
 KEY ACT O

/P

-
 N.O
.

-
 COM

-
 N.C
.

-
 N.O
.

-
 COM

-
 N.C
.

-
 N.O
.

-
 COM

-
 N.C
.

-
 T

AMPE

R

-
 GND

(-

)

-
 DOOR SENS

-
 O/P 1 INHI

B

-
 IN

T.

 L

OC

K

-
 DU OU

T

-
 DOOR BELL IN

-
 EG IN

-
 D

AT

A I/
O

-
 KEY
PAD PW

R

-
 GND

(-

)

-
 12-24V DC

N.O.

ELECTRIC LOCK

1N4004

CATHODE

OUTPUT RELAY 1
N.O. Output for Fail-secure Lock
N.C. Output for Fail-safe Lock

N.C.

OUTPUT 1 OUTPUT 2 OUTPUT 3

DIGITAL KEYPAD

EGRESS BUTTON

MORE EGRESS

BUTTON CAN

BE CONNECTED

IN PARALLEL

DOOR BELL

BUTTON

N.O.

(-)

(-)

(-)

N.O.

N.O.

AD-1312 OR AP-960

(–) COMMON GND

(+) POWER SUPPLY

DATA I/O BUS

DA-2800 OR DA-2801

(DECODE)

this application.

NOTE: 

Connect the 1N4004 as close as possible to the lock in 
parallel with the lock power terminals of the lock to absorb 
the back EMF to prevent it from damaging the keypad. The 
1N4004 is not required if the electric lock is AC operated.
To avoid Electro-Static-Discharge from interfering with the 
operation of the keypad, always ground the (-) terminal of 
the keypad to earth.
Always connect DOOR SENSOR terminal to (-) ground if not 
used.
Always connect TAMPER terminal to (-) ground if not used.
Make 3-wire Connection (+, -, DATA I/O) to the keypad in 
the DK-2800 series. More than one keypads can be 
connected in parallel.

Summary of Contents for DK-2852C

Page 1: ...VANDAL RESISTANT BACK LIT WEATHERPROOF RFID ACCESS CONTROL KEYPAD DK 2852 C D User Manual FOR ELECTRIC LOCK INTER LOCK AND SECURITY SYSTEM INSTALLATIONS AEI PROTECT ON SYSTEMS LIMITED www apo hk com...

Page 2: ...User Code Common User Codes for Output 1 2 User Codes Card For Output 1 2 Examples Programming And Operation Visitor Codes For Output 1 Only Duress Codes For Outputs 1 2 Operation And Function of The...

Page 3: ...ct means that no electricity is connected to it It is prepared for free connections The Relay Output contacts provided in this keypad system are dry contacts N C Normally Closed the contact is closed...

Page 4: ...ation Control Output Relay 2 1A Rating N C N O Contacts for External Door Bell Actuation Control A member of the Tri Tech series keypads compatible with the optional controllers reader keypads for sys...

Page 5: ...hes to ground when duress code is entered You may use it to turn ON an LED lamp and or a small buzzer to notify a guard or connect it to a 24 hour Normally Open protection zone of an alarm system Only...

Page 6: ...ILIARY TERMINALS C KEY ACTIVE a b The Key Active Output switches to ground for 10 seconds whenever a key is touched You may use it to turn ON an LED lamp and or a small buzzer to notify a guard or to...

Page 7: ...the auxiliary readers AR 2802 and the auxiliary reader keypads AR 2806 AR 2807 AR 2809 Total 3 auxiliary readers or reader keypads can be connected in parallel with the Data I O Bus They provide the...

Page 8: ...ECTION TERMINALS 3 Split decoded Access Control Door Lock Description Apart from stand alone operation the DK 2852 can be up graded to high security Split decoded operation with a decoder unit DA 2800...

Page 9: ...Warning The keypad generates door forced open warning instantly once the door is forced to open without a valid user Code Card or egress button The warning lasts as long as the time programmed 1 999 s...

Page 10: ...door position sensing switches for the two doors 16 17 TAMPER N C Tamper Switch Normally Closed Contact A normally closed dry contact while the keypad is secured on its box It is open while keypad is...

Page 11: ...eep 1 Flash 3 Successful Code Card Entry 2 Beeps 2 Flashes 4 Unsuccessful Code Card Entry 5 Beeps 5 Flashes 5 Power Up Delay Continuous Beeps Continuous Flashes 6 Output Relay Activation 1 Second Long...

Page 12: ...User Code Operation Media 3 A secondary user code can be repeatedly used for a group of cards in a department Owner can make a proprietary department code for each department in a company Only the sta...

Page 13: ...with proprietary user code approach is ideal for the area that high security is the main concern This operation mode can also report Duress Alarm by keying in the duress code instead of Secondary user...

Page 14: ...r power has been applied It is the time frame designed for setting the keypad to programming mode with DAP code See the details of DAP CODE 2 8 2 8 below 1 The keypad gives continuous beeps for 1 minu...

Page 15: ...ogramming Code The system back to normal opration after programming Pacifier Tone ON OFF 7 1 FUNCTION MODE 0 NO Notification 2 2 Short Beeps 1 1 Second Long Beep FUNCTION MODE 0 OFF 1 ON FUNCTION MODE...

Page 16: ...ting system program It can not be changed in any ways PROGRAMMING SUMMARY CHART LOCATION FUNCTION ENTRY LIMITS CODE OPTIONS CODE ENTRY FACTORY DEFAULT 0 1 Master Code 4 8 Digits MASTER CODE NIL 0 2 Su...

Page 17: ...sed with the EM Card It is for example here only f Confirm the Card Code is stored 2 beeps 6 Record an EM Card Commom User Code to Operate The Output 1 for Door Open a b c d e a 10 Programming Locatio...

Page 18: ...be used to reset an operating output timer instantly Output 1 Activates or Resets Output 2 Activates or Resets Optional Functions Controlled by Super User Code for Output 1 Apart from controlling of t...

Page 19: ...LIDATION Press key once Two beep confirms the entry or 3 2 1 CLOSE PROGRAMMING MODE Always close programming mode with to set system back to normal Operation after programming The button is equivalent...

Page 20: ...eps confirms the entry EXAMPLES Example 1 Set Egress Button in Momentary contact of 5 seconds with delay warning beep a b c d a Egress function programming b Momentary contact with warning c Delay tim...

Page 21: ...card once and confirm It does not require the ID number The Card includes the combinations of 1 Card Only 2 Card Secondary User Code and 3 Card Common User Code 1 2 5 4 3 Location Clearing takes few s...

Page 22: ...o operation mode a b a Key in the Private User Code 1 2 3 4 b Confirm it with the key Output 2 activates Read Card Read Card High Traffic Passage A short buffer time may be necessary for opening a doo...

Page 23: ...o prevent unattended leaving shoplifting and unauthorized use of the emergency exits The Intelligent Egress Button can be programmed to do something to get attention from the person on duty before the...

Page 24: ...e Whole Group of Users Whole group of users including the Codes and Cards can be cleared with the following command a b c a The User Group 1 10 is selected to be cleared 20 for Group 2 b Key in the Gr...

Page 25: ...on 72 1 LOCATION Key in Location 2 FUNCTION MODES FOR OUTPUT ANNOUNCER Output announcer gives notification beep on the operation status of the outputs There are two notification modes available for th...

Page 26: ...User Codes must be in 5 digits as well All other User Codes not in 5 digits become invalid When the number of digits reaches the system will check the User Code automatically Good for high traffic acc...

Page 27: ...e code entry The Duress Codes MUST be in the same digit length with the Master Code for Auto Mode code entry Always set a Duress Code that is easy to remember in Panic Situation Only one number differ...

Page 28: ...Output 1 b Duress Code ID c The Duress Code e Entry Confirmation iii Pause the real time inhibition manually The real time inhibition can be stopped temporarily if require such as the staff work overt...

Page 29: ...t in emergency START STOP TIMES FOR DAILY INHIBITION OF OUTPUT 1 Location 56 Setting with start and stop times into the keypad the real time inhibition period for output 1 will recycle daily until the...

Page 30: ...our real time clock provides the daily time base for starting and stopping the function of inhibition to relay output 1 mainly for electric door lock strike No real time clock setting is required if d...

Page 31: ...nterference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful inter...

Reviews: