In previous figure we demonstrate how to configure an ADAM-4017+ (or ADAM-
4117) which slave ID is 1 and an ADAM-4055 which slave ID is 2 as the Modbus
slave devices connected to WISE-4051.
ADAM-4017+ (or ADAM-4117) is an 8-ch analog input Modbus I/O modules, the
Modbus address of AI0~AI7 are 40001~40008. In the
Rule Setting
page, we config-
ure the
Slave ID
= 1;
Type
= 03 Holding Registers, since the Modbus address 40001
is start from 4;
Start Address
= 1 and
Length
= 8 for the address 40001~40008;
R/
W
= R, since this address is for analog input which is read only;
Scan Interval
=
1000ms for polling every second;
Mapping Channel
= 0, to mapping the data from
AI0~7 of ADAM-4017+ to channel 0~7 of Word Status; and check the
Log
to log the
data from ADAM-4017+.
ADAM-4055 is an 8-ch digital input and 8-ch digital output Modbus I/O modules, the
Modbus address of DI0~DI7 are 00001~00008; the Modbus address of DO0~DO7
are 00017~00024. Since the address is not continuously, so we are going to config-
ure digital input as one rule, and digital output as another rule.
For digital input channels: In the
Rule Settin
g page, we configure the
Slave ID
= 2;
Type
= 01 Coil Status, since the Modbus address 00001 is start from 0;
Start
Address
= 1 and
Length
= 8 for the address 00001~00008;
R/W
= R, since this
address is for digital input which is read only;
Scan Interval
= 1000ms for polling
every second;
Mapping Channel
= 0, to mapping the data from DI0~7 of ADAM-
4055 to channel 0~7 of Bit Status; and check the
Log
to log the data from ADAM-
4055. Please be noted that the Bit Status and Word Status have individual channel
number, so the Word Status for ADAM-4017+ and the Bit Status for ADAM-4055 are
all start from 0.
For digital output channels: In the
Rule Setting
page, we configure the
Slave ID
= 2;
Type
= 01 Coil Status, since the Modbus address 00017 is start from 0;
Start
Address
= 17 and
Length
= 8 for the address 00017~00024;
R/W
= R/W, since this
address is for digital output which can be wrote and read, you can also configured as
W if you don't want to read back the value;
Scan Interval
= 1000ms for polling every
second;
Mapping Channel
= 8, to mapping the data from DO0~7 of ADAM-4055 to
channel 8~15 of Bit Status; and check the
Log
to log the data from ADAM-4055.
Please be noted that the channel 0~7 of Bit Status have been occupied by previous
rule, so you should assign the channel number from channel 8~31.
Summary of Contents for WISE-4000 Series
Page 1: ...User Manual WISE 4000 Series IoT Ethernet I O Module ...
Page 9: ...Chapter 1 1 Product Overview ...
Page 17: ...Chapter 2 2 Product Specifications ...
Page 42: ...WISE 4000 User Manual 34 2 9 4 Block Diagram Figure 2 35 WISE 4060 Block Diagram ...
Page 43: ...Chapter 3 3 Hardware Installation ...
Page 51: ...Chapter 4 4 System Configuration ...
Page 100: ...WISE 4000 User Manual 92 ...
Page 101: ...Appendix A A I O Modbus Mapping Table ...
Page 124: ...WISE 4000 User Manual 116 ...