line. The throttling valve can be a gate
valve or a ball valve.
h.
With the throttling valve installed, fully
close the valve and then engage the
pump motor. Slowly open the throttling
valve and monitor the motor amps as
displayed on the amp meter until the
actual motor amps equal the listed full
load amp rating of the motor. The process
flow is now correctly adjusted. The valve
should remain in this position during
operation.
6.
LOW PROCESS FLOW: The minimum
recommended process flow rate is 10 GPM.
Process restrictions may limit the flow to less than
10 GPM. We recommend the addition of bypass
lines to raise the flow rate to 10 GPM. The best place to add bypass lines are on
the extra ports on the molding machine manifold. If extra ports are not available,
add a tee in the To Process and From Process lines, install a bypass line
between the two tees with a throttling valve. Adjust the valve for a minimum of 10
GPM.
3.3 INSTRUMENT
Motor name plate
Unit “On/Off”
Switch
Temperature
Display
Machine Sta-
tus Lights
Setpoint Adjust-
ment Buttons
Summary of Contents for Sentra SK Series
Page 2: ......
Page 6: ...Page 6 THIS PAGE INTENTIONALLY BLANK ...
Page 20: ...Page 20 THIS PAGE INTENTIONALLY BLANK ...
Page 30: ...Page 30 THIS PAGE INTENTIONALLY BLANK ...
Page 36: ...Page 36 THIS PAGE INTENTIONALLY BLANK ...
Page 68: ...Page 68 THIS PAGE INTENTIONALLY BLANK ...
Page 69: ...END 2017 ADVANTAGE ENGINEERING INC RE 01272017 ...
Page 70: ......