Wolf Series RS-485 Remote I/O Module
Wolf series Remote IO Module User's Manual
78
44110
(0x100D)
Status of system watch dog
0x0001: Timeout 0x0000: Normal
R/W
-
44111
(0x100E)
Counter of communication frame
R
0x0000
3.7.6.2 W-M1B112 Modbus address table
Coil (0xxxx) / (1xxxx)
Address
Function
R/W
Initial
Value
00537
(0x0218)
Allow calibration
0: Disallow 1: Allow
R/W
0
00641~00656
(0x0280~0x028F)
CH0~CH15 Out of range
0: normal 1: out of range
R
0
Holding Register( 4xxxx) / Input Register(3xxxx)
Address
Function
R/W
Initial
Value
30513~30528
40513~40528
(0x0200~0x020F)
AI CH0 ~ CH15 Value
R
-
40705~40720
(0x02C0~0x02CF)
CH0~CH15 Input signal type
R/W
0x0106
40737
(0x02E0)
AI Result format of measurement
0x0000: Hex 0x0001: Engineering
R/W
0x0000
40577
(0x02F4)
CH0~CH15 Calibrate maximum value
to each channel. (Each bit map to
corresponding channel)
Ex. Bit 0 = 1, Calibrate CH0.
Bit 1 = 1, Calibrate CH1.
W
0x0000
40578
(0x02F5)
CH0~CH15 Calibrate 0 level to each
channel. (Each bit map to corresponding
channel)
W
0x0000
40579
(0x02F6)
CH0~CH15 Perform internal calibration
to each channel. (Each bit map to
corresponding channel)
W
0x0000