Wolf Series RS-485 Remote I/O Module
Wolf series Remote IO Module User's Manual
76
0x0108
± 1 V
-10000
10000
3.7.5.3 Signal Value
Once completing the setup, please enter the measured value. This is to enable/
disable the channel(s) and check if the value is out-of-range (valtage contact loss is
deemed to be “out of range”). Modbus command as following:
Address
Function
R/W Initial Value
40737
(0x02E0)
AI Value format
0x0000: Hex 0x0001: Engineering
R/W
0x0000
00641~00656
(0x0280~0x028F)
CH0~CH15 Out of range
0: normal 1: out of range
R
0
30513~30528
40513~40528
(0x0200~0x020F)
AI CH0 ~ CH7 Value
R
-
3.7.6 MODBUS Address
3.7.6.1 W-M1B111 Modbus address table
Coil (0xxxx) / (1xxxx)
Address
Function
R/W
Initial
Value
00537
(0x0218)
Allow calibration
0: Disallow 1: Allow
R/W
0
00641~00648
(0x0280~0x0287)
CH0~CH7 Out of range
0: normal 1: out of range
R
0
Holding Register( 4xxxx) / Input Register(3xxxx)
Address
Function
R/W
Initial
Value
30513~30520
40513~40520
(0x0200~0x0207)
AI CH0 ~ CH7 Value
R
-
40705~40712
(0x02C0~0x02C7)
CH0~CH7 Input signal type
R/W
0x0106