Wolf Series RS-485 Remote I/O Module
Wolf series Remote IO Module User's Manual
67
Address
Function
R/W Initial Value
40737
(0x02E0)
AI Value format
0x0000: Hex 0x0001: Engineering
R/W
0x0000
00641~00656
(0x0280~0x0287)
CH0~CH15 Out of range
0: normal 1: out of range
R
0
30513~30528
40513~40528
(0x0200~0x020F)
AI CH0 ~ CH15 Value
R
-
3.6.6 MODBUS Address
3.6.6.1 W-M1B109 Modbus address table
Coil (0xxxx) / (1xxxx)
Address
Function
R/W
Initial
Value
00537
(0x0218)
Allow calibration
0: Disallow 1: Allow
R/W
0
00641~00648
(0x0280~0x0287)
CH0~CH7 Out of range
0: normal 1: out of range
R
0
Holding Register( 4xxxx) / Input Register(3xxxx)
Address
Function
R/W
Initial
Value
30513~30520
40513~40520
(0x0200~0x0207)
AI CH0 ~ CH7 Value
R
-
40705~40712
(0x02C0~0x02C7)
CH0~CH7 Input signal type
R/W
0x0201
40737
(0x02E0)
AI Result format of measurement
0x0000: Hex 0x0001: Engineering
R/W
0x0000
40577
(0x02F4)
CH0~CH7 Calibrate maximum value to
each channel. (Each bit map to
corresponding channel)
Ex. Bit 0 = 1, Calibrate CH0.
Bit 1 = 1, Calibrate CH1.
W
0x0000