Wolf Series RS-485 Remote I/O Module
Wolf series Remote IO Module User's Manual
60
(0x0240~0x0247) unit: 0.01
℃
, Range: -50.0
℃
~ 50.0
℃
40609 ~ 40616
(0x0260~0x0267)
CJC Compensation
unit: 0.01
℃
, Range: -50.0
℃
~ 50.0
℃
R/W
0x0000
40641
(0x0280)
CJC Value, Unit : 0.01
℃
R
-
40642
(0x0281
CH8~CH15 CJC Value, Unit : 0.01
℃
40657
(0x0290)
Module CJC Compensation
unit: 0.01
℃
, Range: -50.0
℃
~ 50.0
℃
40705~40720
(0x02C0~0x02CF)
CH0~CH15 Input signal type
R/W
0x0106
40737
(0x02E0)
AI Result format of measurement
0x0000: Hex 0x0001: Engineering
R/W
0x0000
40577
(0x02F4)
CH0~CH7 Calibrate maximum value to
each channel. (Each bit map to
corresponding channel)
Ex. Bit 0 = 1, Calibrate CH0.
Bit 1 = 1, Calibrate CH1.
W
0x0000
40578
(0x02F5)
CH0~CH15 Calibrate 0 level to each
channel. (Each bit map to corresponding
channel)
W
0x0000
40579
(0x02F6)
CH0~CH15 Perform internal calibration
to each channel. (Each bit map to
corresponding channel)
W
0x0000
40580
(0x02F7)
CH0~CH15 Calibration in process
(Each bit map to corresponding
channel)
0: No operation
1: Calibration in process
R
-
44097
0x1000
Firmware version 2 Bytes
High Byte
Low Byte
Main version
Sub-version
R
-
44098~44105
(0x1001~0x1008)
Module name 16 Bytes (16 ASCII char) R
-
44106
(0x1009)
Modbus response delay time (unit: ms)
Range: 0~30
R/W
0