Wolf Series RS-485 Remote I/O Module
Wolf series Remote IO Module User's Manual 135
000129
(0x0080)
DI CH0~CH15 Latch Clear
W
0
000145~000160
(0x0090~0x009F)
DI CH0~CH15 Counter Clear
W
All 0
00257~00272
(0x0100~0x010F)
DO CH0~CH15 Output Status
R/W
-
Holding Register (4xxxx) / Input Register (3xxxx)
Address
Function
R/W Initial Value
30001~30016
40001~40016
(0x0000~0x000F)
DI CH0~CH15 DI Counter Value
R
All 0x0000
40129
(0x0080)
DI CH0~CH15 Input Active Value Define
0x0000: input value 0 for non-signal;
0x0001: input value 1 for non-signal;
R/W 0x0000
40137
(0x0088)
DI CH0~CH15 Counter Edge Define
(Each bit map to corresponding channel)
1=rising edge 0=falling edge
R/W 0x0000
40257
(0x0100)
DO CH0~CH15 Power On Value
(Each bit map to corresponding channel)
R/W All 0x0000
40259 (0x0102)
DO CH0~CH15 Safety Output Value
(Each bit map to corresponding channel)
R/W All 0x0000
40385
(0x0180)
DO CH0~CH15 Output Active Value
0x0000: output value 1 for relay active;
0x0001: output value 0 for relay active;
R/W All 0x0000
44097
0x1000
Firmware version 2 Bytes
High Byte
Low Byte
Main version
Sub-version
R
-
44098~44105
(0x1001~0x1008)
Module name 16 Bytes (16 ASCII char)
R
-
44106
(0x1009)
Modbus response delay time (unit: ms)
Range: 0~30