2.2  Operating Conditions 

2.2.1 

Fire Alarm Condition 

  [Fire Detected] 
FIRE STARTED: ZONE 1 
 
TOTAL FIRES: 1 

The display shows location / origin of the fire alarm and the total 
number of zones in a fire alarm condition. 

If two or more zones enter the fire alarm condition, the display also 
shows the location of the last zone to enter a fire alarm condition. 

In addition, the General Fire LED and the respective Zone Fire 
LED will be illuminated. 

  [Release Status] 
STAGE-1 

 

 

  [Fire Detected] 
FIRE STARTED: ZONE 1 
LAST FIRE   : ZONE 3 
TOTAL FIRES : 2 

The status of the extinguishant release is also indicated. If a fire 
alarm occurs in a zone that has no effect on the extinguishant 
control then the display shows UNAFFECTED. 

  [Release Status] 
STAGE-1 

 

 

The fire alarm bells / sounders will activate (depending on how they are programmed to respond). 

To silence the internal buzzer, press the 

 button (if configured) or the MUTE button on the control panel. 

To silence the bells, press the SILENCE button on the control panel. 

To reset the panel, press the RESET button on the control panel. 

NOTE: If the programming of the panel is such that the release condition is immediately invoked on detection of 
a single fire alarm, then the display will immediately show the release status information. 

2.2.2 

Release / Activated Condition 

The activated condition is established when one or more fire alarms have occurred or when the manual release 
button is pressed.  

The number of zones, and which zones, that must be in a fire alarm condition before the activated condition is 
invoked depends on the installation programming of the panel. 

  [Release status] 
RELEASE IMMINENT.. 
 

-15 

When the activated condition is established, the display indicates 
that the release is imminent and also shows a countdown timer 
with the number of seconds remaining before the extinguishant is 
released. 

In addition, the Release Imminent LED flashes. 

If programmed, the bells / sounders will ring with pulsed alert tone. 

 

RELEASE ACTIVATED 
00:00:05 Elapsed 

When the countdown timer has elapsed, the actuating output is 
activated to start the release of the extinguishant. 

The display now shows the time elapsed since the release of 
extinguishant commenced. 

In addition, the Release Imminent LED turns ON steady. 

 
 
 
 

 

 

 

Summary of Contents for ExGo Series

Page 1: ...www advancedco com Remote Status Indicators Installation and Commissioning The operation and functions described in this manual are available from Software Version Ex 3000 V2 05C onwards...

Page 2: ...f 1 Relay Outputs Optional 2x rated at 1A 30VAC DC max 10mA 5V min programmable requires EXP 007 Key Switches 1x programmable Optional Fitted Optional Fitted Manual Release No No Yes Yes External Inpu...

Page 3: ...Abort Condition 10 2 2 5 Fault Condition 10 2 2 6 Warning Condition 10 2 3 LEVEL 1 MENU FUNCTIONS 11 2 3 1 Navigating through Level 1 Menus 11 2 3 2 View 11 2 3 2 1 Faults 11 2 3 2 2 Disables 12 2 3...

Page 4: ...se of the Ex 3000 Series Remote Status Indicating Panels The Ex 3020 is an RSI with Liquid Crystal Display and LED Indicators The Ex 3021 is an RSI with Liquid Crystal Display LED Indicators and Mode...

Page 5: ...3030 but is without the Manual Release function 2 1 1 1 Display The LCD along with the LED Indicators shows the operating status of the system Examples of the information presented is shown below Nor...

Page 6: ...anel has detected the folw of the extinguishant released TIMER HELD Yellow Indicates that the imminent release of extinguishant is temproraily suspended ABORTED Yellow Indicates that the imminent rele...

Page 7: ...ions of these are programmable and the installer will have inserted a label to indicate their use Typical uses are AUTO MANUAL MANUAL ONLY Selection EXTRACT OVERRIDE Depending on the key switch mechan...

Page 8: ...nel press the RESET button on the control panel NOTE If the programming of the panel is such that the release condition is immediately invoked on detection of a single fire alarm then the display will...

Page 9: ...n on the control panel Section 4 12 2 Reset of the Activated Condition Release Signal NOTE In accordance with EN 12094 1 the ECD shall not permit a reset until either the RELEASED condition has been e...

Page 10: ...UNAFFECTED NOTE The fault condition is non latching except System Fault and the indications will automatically be cleared when the fault is remedied Press the RESET key to clear a System Fault NOTE If...

Page 11: ...u option and then press the button to select it Press the button from within a menu option to return to the previous menu The display will revert to the status mode display after 60 seconds on no acti...

Page 12: ...e warning conditions Press the buttons to scroll through the list of warnings Press the button to return to the previous menu 2 3 2 4 Software Versions The display shows the revision of software insta...

Page 13: ...Indicator ZONE 2 ZONE 3 SYSTEM FAULT MODE SUPPLY INPUTS 485 IN 485 OUT USB REBOOT SWITCH CONTRAST ADJUST RUN PROG COVER FIXING SCREWS The panel comprises a back box and cover chassis assembly The chas...

Page 14: ...n the diagram below Remove the chassis before installing the enclosure retain in a safe place Ensure that there is sufficient space to allow the cover to be removed opened when the panel is finally mo...

Page 15: ...a Safety Extra Low Voltage SELV supply Connect the 24V DC supply feed input to the SUPPLY 24V and 0V terminals on the interface card Use cables of sufficient size to ensure that the power input voltag...

Page 16: ...t conditions see typical arrangement below EOL 6800 Maximum line impedance 50 Connect to volt free switches relay contacts only MANUAL ONLY AUTO MANUAL DISABLED FAULT TIMER HELD ABORTED RELEASE IMMINE...

Page 17: ...description into the pocket in the fascia label Plug the connector into the respective connector on the card Key Switch assemblies are available in both trapped and non trapped versions The function...

Page 18: ...www advancedco com 18 This page is intentionally left blank...

Page 19: ...www advancedco com 19 USER NOTES...

Page 20: ...ystem Emergency Abort Device Activation of Alarm Devices with Different Signals Response delay activated condition maximum 3s Response delay triggering of outputs maximum 1s EN54 2 1997 A1 Control and...

Reviews: