background image

 

 

www.advancedco.com 

12 

2.3.2.2  Disables 

  [Disable List] 

Zone 1      DISABLED 

Man Release DISABLED 
  
 
 
 

If there are disablement conditions present, the display will show 
the number of conditions and a list of the disablements. 

Press the 



 buttons to scroll through the list of disablements. 

Press the 

 button to return to the previous menu. 

Disable conditions can only be set on the control panel. 

2.3.2.3  Warnings 

[Warning Status] 
       1 of 2 

VALVE MONITOR INPUT

.

 

>VALVE CLOSED      

.  

PRESSURE MONITOR 
>LOW PRESSURE 
 

If there are warning conditions in the extinguishant system present, 
the display will show the number of conditions and a list of the 
warning conditions. 

Press the 



 buttons to scroll through the list of warnings. 

Press the 

 button to return to the previous menu. 

 

2.3.2.4  Software Versions 

The display shows the revision of software installed in this RSI. The software revisions of the control panel and 
all RSI units can be viewed simultaneously on the panel. 

[Software Versions] 
RSI-6 : 02.00 
 
 
 
 
 

On selection, the display shows a list containing the panel and any 
configured remote status indicators along with the version of 
software installed in each device. 

Press the 



 buttons to scroll through the list of entries. 

Press the 

 button to return to the previous menu. 

2.3.3 

LED Test 

On selection, the front panel LED Indicators will be illuminated for a short period of time.  

2.3.4 

Exit 

On selection, the display reverts to the normal status display indications. 

 

Summary of Contents for ExGo Series

Page 1: ...www advancedco com Remote Status Indicators Installation and Commissioning The operation and functions described in this manual are available from Software Version Ex 3000 V2 05C onwards...

Page 2: ...f 1 Relay Outputs Optional 2x rated at 1A 30VAC DC max 10mA 5V min programmable requires EXP 007 Key Switches 1x programmable Optional Fitted Optional Fitted Manual Release No No Yes Yes External Inpu...

Page 3: ...Abort Condition 10 2 2 5 Fault Condition 10 2 2 6 Warning Condition 10 2 3 LEVEL 1 MENU FUNCTIONS 11 2 3 1 Navigating through Level 1 Menus 11 2 3 2 View 11 2 3 2 1 Faults 11 2 3 2 2 Disables 12 2 3...

Page 4: ...se of the Ex 3000 Series Remote Status Indicating Panels The Ex 3020 is an RSI with Liquid Crystal Display and LED Indicators The Ex 3021 is an RSI with Liquid Crystal Display LED Indicators and Mode...

Page 5: ...3030 but is without the Manual Release function 2 1 1 1 Display The LCD along with the LED Indicators shows the operating status of the system Examples of the information presented is shown below Nor...

Page 6: ...anel has detected the folw of the extinguishant released TIMER HELD Yellow Indicates that the imminent release of extinguishant is temproraily suspended ABORTED Yellow Indicates that the imminent rele...

Page 7: ...ions of these are programmable and the installer will have inserted a label to indicate their use Typical uses are AUTO MANUAL MANUAL ONLY Selection EXTRACT OVERRIDE Depending on the key switch mechan...

Page 8: ...nel press the RESET button on the control panel NOTE If the programming of the panel is such that the release condition is immediately invoked on detection of a single fire alarm then the display will...

Page 9: ...n on the control panel Section 4 12 2 Reset of the Activated Condition Release Signal NOTE In accordance with EN 12094 1 the ECD shall not permit a reset until either the RELEASED condition has been e...

Page 10: ...UNAFFECTED NOTE The fault condition is non latching except System Fault and the indications will automatically be cleared when the fault is remedied Press the RESET key to clear a System Fault NOTE If...

Page 11: ...u option and then press the button to select it Press the button from within a menu option to return to the previous menu The display will revert to the status mode display after 60 seconds on no acti...

Page 12: ...e warning conditions Press the buttons to scroll through the list of warnings Press the button to return to the previous menu 2 3 2 4 Software Versions The display shows the revision of software insta...

Page 13: ...Indicator ZONE 2 ZONE 3 SYSTEM FAULT MODE SUPPLY INPUTS 485 IN 485 OUT USB REBOOT SWITCH CONTRAST ADJUST RUN PROG COVER FIXING SCREWS The panel comprises a back box and cover chassis assembly The chas...

Page 14: ...n the diagram below Remove the chassis before installing the enclosure retain in a safe place Ensure that there is sufficient space to allow the cover to be removed opened when the panel is finally mo...

Page 15: ...a Safety Extra Low Voltage SELV supply Connect the 24V DC supply feed input to the SUPPLY 24V and 0V terminals on the interface card Use cables of sufficient size to ensure that the power input voltag...

Page 16: ...t conditions see typical arrangement below EOL 6800 Maximum line impedance 50 Connect to volt free switches relay contacts only MANUAL ONLY AUTO MANUAL DISABLED FAULT TIMER HELD ABORTED RELEASE IMMINE...

Page 17: ...description into the pocket in the fascia label Plug the connector into the respective connector on the card Key Switch assemblies are available in both trapped and non trapped versions The function...

Page 18: ...www advancedco com 18 This page is intentionally left blank...

Page 19: ...www advancedco com 19 USER NOTES...

Page 20: ...ystem Emergency Abort Device Activation of Alarm Devices with Different Signals Response delay activated condition maximum 3s Response delay triggering of outputs maximum 1s EN54 2 1997 A1 Control and...

Reviews: