www.advancedco.com
6
2.1.1.2 LED Indications
The LED Status Indications show the basic operational state of the panel and whether the panel is in a fire
alarm, fault, disabled or test condition.
2.1.1.2.1 GENERAL STATUS
Function
Colour
Description
SYSTEM FAULT
Yellow
Indicates the presence of a system fault
2.1.1.2.2 DETECTION ZONE STATUS
Function
Colour
Description
FIRE
Red
Indicates that the system has detected a fire alarm condition in the respecitve zone
2.1.1.2.3 EXTINGUISHANT
Function
Colour
Description
RELEASE IMMINENT
Red
Indicates (flashing) that the release of extinguishant is imminent. The indication will turn to
steady when the signal to release the extinguishant has been activated.
RELEASED
Red
Indicates that the release of extinguishant has occurred and the panel has detected the folw
of the extinguishant released.
TIMER HELD
Yellow
Indicates that the imminent release of extinguishant is temproraily suspended.
ABORTED
Yellow
Indicates that the imminent release of the extinguishant has been aborted.
DISABLED
Yellow
Indicates that the extinguishant release control signal has been disabled. The release of
extinguishant is prevented even if a fire alarm or manual release are present.
FAULT
Yellow
Indicates that the system has detected a fault condition within part of the extinguishing
system and control device (ECD) circuits.
MANUAL ONLY
Yellow
Indicates that the extinguishant can only be released by means of a manual release button.
AUTO + MANUAL
Yellow
Indicates that the extinguishant can be released by both the automatic detection of a fire
alarm and by means of a manual release button.
2.1.1.3 Manual Release Button (Ex-3030 Only)
To manually release the extinguishant, pull down the flap and press the button marked with the circle.