Thyro-AX 2A and Thyro-AX 3A (load with common star point without
neutral conductor)
NUMBER OF
PARALLEL
LOAD RESIS-
TANCES
I
LOAD NOMINAL
/
I
TYPE CONTROLLER
*
U
LOAD NOMINAL
/
U
TYPE CONTROLLER
*
RESISTANCE
CHANGE IN
FAULT**
RECOM-
MENDED
SETTINGS
FOR R_MAX
1
20%
40%
unlimited
R
Load
+50%
2
20%
40%
+67%
R
Load
+33%
3
40%
40%
+33%
R
Load
+18%
4
40%
40%
+22%
R
Load
+15%
Thyro-AX 2A and Thyro-AX 3A (load in delta connection)
NUMBER OF
PARALLEL
LOAD RESIS-
TANCES
I
LOAD NOMINAL
/
I
TYPE CONTROLLER
*
U
LOAD NOMINAL
/
U
TYPE CONTROLLER
*
RESISTANCE
CHANGE IN
FAULT**
RECOM-
MENDED
SETTINGS
FOR R_MAX
1
20%
40%
+73%
R
Load
+36%
2
20%
40%
+31%
R
Load
+16%
3
60%
40%
+20%
R
Load
+15%
Thyro-AX 3A (load with common star point with neutral conductor /
open delta connection)
NUMBER OF
PARALLEL
LOAD RESIS-
TANCES
I
LOAD NOMINAL
/
I
TYPE CONTROLLER
*
U
LOAD NOMINAL
/
U
TYPE CONTROLLER
*
RESISTANCE
CHANGE IN
FAULT**
RECOM-
MENDED
SETTINGS
FOR R_MAX
1
20%
40%
unlimited
R
Load
+50%
2
20%
40%
+100%
R
Load
+50%
3
40%
40%
+50%
R
Load
+25%
4
40%
40%
+33%
R
Load
+18%
5
40%
40%
+25%
R
Load
+15%
* min value for 100% setpoint
** partial load fault
TAB. 10 LOAD RESISTANCE
NOTE
- In operating mode VAR, the monitoring is blocked for large control
angles (for load with neutral conductor alpha > 140°, for load wit-
hout neutral conductor alpha > 117°).
- In the operating mode TAKT the monitoring is blocked for low
setting times (Ts) (by 2-phase devices Ts< 2 periods).