Preliminary information
Page
6
of
14
GSS0608
Version: 1.3
3 Requirements regarding installation location
(Detail from the instruction manual)
The system is designed for stationary use in an outdoor area. Make certain that the specified
environmental conditions are maintained at all times. Use in non-specified environments,
e.g. on board ships, in explosive atmospheres or at high altitude (see the climatic environmental
conditions) is prohibited.
CAUTION
Hazard due to condensation!
Condensation may form if the system has not had sufficient time to settle to the
environmental conditions following transport or before it is put into operation
again. (Connection to AC supply is required.)
3.1.1 Environmental conditions
Observe the environmental conditions information in the technical data (
3.1.2 Requirements regarding installation location
Please note that the battery system may not be set up and operated
•
in buildings, garages, courtyards and other covered structures
•
in areas where there is a risk of flooding
•
in areas where there is a risk of fire and explosion
•
in the vicinity of combustible materials
•
and in areas with sandstorms
•
in permanent residential areas
•
in the vicinity of escape routes
.
Installation conditions:
•
The "Commissioning requirements" checklist must be completed and signed
(
•
The system is only suitable for outdoor installation.
•
Observe the following floor space requirements for the system:
−
The floor space is to be constructed at the installation location in accordance with the local
conditions and technical data (
−
Wind-protected (e.g. in the lee of a building)
−
The floor space is exactly horizontal.
−
Cable entry is from below.
−
The floor space has the required load capacity for the 1.25 t weight of the system and has
to withstand this load permanently.
If applicable, also take into account the weight of the means of transport.
−
Sufficient drainage is available.
•
Earthing via ring earth electrode for flexible connection cable (min. 16 mm²) according to
national and local regulations and conditions must be in place.
•
Note that ventilation openings must be kept clear.
−
The air at the ventilation openings must be able to circulate freely.
−
During the entire operating time, no leaves, dirt, etc. must be sucked in from the ventilation
openings.
•
Protect the system against penetrating water (groundwater or flood hazard area).
Summary of Contents for StoraXe PowerBooster GSS0608
Page 1: ...StoraXe PowerBooster Compact storage system GSS0608 ...
Page 4: ......
Page 14: ...Preliminary information Page 10 of 14 GSS0608 Version 1 3 6 Bottom view of unit ...
Page 15: ...Preliminary information Page 11 of 14 GSS0608 Version 1 3 7 Checklist for commissioning ...
Page 16: ...Preliminary information Page 12 of 14 GSS0608 Version 1 3 ...
Page 21: ......
Page 22: ......
Page 118: ......
Page 120: ......
Page 121: ......
Page 122: ......
Page 123: ......
Page 124: ......
Page 125: ......
Page 126: ......
Page 127: ......
Page 128: ......
Page 129: ......
Page 138: ......
Page 139: ......