Adp HED Series Installation Instructions Manual Download Page 7

VENT TERMINATION ON SINGLE−WALL VERTICAL VENT RUNS

 

 

SINGLE−WALL VENT PIPE WITH

 

SINGLE−WALL VENT PIPE WITH

 

SINGLE−WALL TERMINATION

 

DOUBLE−WALL (TYPE B−1) TERMINATION

 

 

ROOF FLASHING

 

 

ROOF PITCHED

 

FROM 0" TO 45"

 

 

ROOF FLASHING

 

 

ROOF PITCHED

 

FROM 0" TO 45"

 

 

 

12" MAX  

2” CLEARANCE                                                          

  

         

 

THIMBLE

 

 

SEAL JOINT BETWEEN SINGLE−WALL VENT AND B" VENT TERMINATION

 

AND THE OPEN SPACE BETWEEN THE SINGLE WALL VENT PIPE AND

 

THE OUTER PIPE OF THE B" VENT TERMINATION.

 

 

 

 

 

 

 

 
 

CLEARANCE TO BE 

AS  SPECIFIED  ON 

TYPE B" VENT PIPE.

 

 

FIGURE 3

 

 

7 −  The  vent  pipe  must  extend  at  least  3  feet  (1m) 

above the highest point where it passes through a 

roof  of  a  building.  The  vent  must  also  extend  at 

least  two  feet  higher  than  any  part  of  a  building 

within  a  horizontal  distance  of  10  feet  (3.05  m) 

unless otherwise specified by the ANSI Z223.1 or 

CSA−B149  installation  compliance  codes.  The 

vent  must  extend  at  least  5  feet  (1.53  m)  above 

the highest connected equipment flue collar.

 

 

TABLE 3

 

MAXIMUM HORIZONTAL VENT CONNECTOR AND

 

HORIZONTAL VENT PIPE LENGTHS

 

 

 

 

HED−75 through

 

HED−200 through

 

 

No. of

 

  

−150

 

 

−300

 

 

 

 

 

 

 

 

Elbows

 

   

 

 

 

 

 

ft

 

 

m

 

ft

 

 

m

 

 

 

 

 

 

 

 

   

 

 

 

 

 

 

1

 

 

25

 

 

7.6

 

35

 

 

10.7

 

 

 

   

 

 

 

 

 

 

2

 

 

20

 

 

6.1

 

30

 

 

9.1

 

 

 

   

 

 

 

 

 

 

3

 

 

15

 

 

4.6

 

25

 

 

7.6

 

 

 

   

 

 

 

 

 

 

4

 

 

10

 

 

3.0

 

20

 

 

6.1

 

 

 

   

 

 

 

 

 

 

5

 

 

5

 

 

1.5

 

15

 

 

4.6

 

 

 

   

 

 

 

 

 

 

6

 

 

−−

 

 

−−

 

10

 

 

3.0

 

 

 

   

 

 

 

 

 

 

7

 

 

−−

 

 

−−

 

5

 

 

1.5

 

 

 

   

 

 

 

 

 

 

 

8−

 

When  the  length  of  a  single-wall  vent,  including 

elbows,  exceeds  the  length  shown  in  table  4,  the 

vent shall be insulated along its entire length with a 

minimum  of  1/2"  thick  foil  faced  fiberglass  1–1/2# 

density insulation.

 

 

TABLE 4

 

 

MAXIMUM LENGTH UNINSULATED VENT CONNECTOR

 

 

HORIZONTAL VENTING

 

 

NOTE

  −  Common  venting  is  not  allowed  when 

horizontally venting the duct heater.

 

 

If  the  HED  duct  heater  is  to  be  horizontally  vented,  a 

positive pressure may be created in the vent. The duct 

heater,  when  installed  with  horizontal  venting,  will 

perform as a category III appliance.

 

 

1 −  

Special vent materials approved for use with

 

Category III appliances may be used with these 

units. 

Refer to table 7 for venting components.

 

 

2 −  If possible, do not terminate the horizontal vent 

through a wall that is exposed to prevailing wind.

 

 

Exposure  to  excessive  winds  can  affect  unit 

performance.  If  such  a  termination  is  necessary, 

use  a  wind  block  to  protect  the  vent  termination 

from direct winds.

 

 

3 −  Vent  termination  must  be  free  from  obstructions 

and at least 12" (30.5 cm) above grade level and 

maximum snow height.

 

 

4 −  Do not terminate vent directly below roof eaves or 

above a public walkway, or any other area where 

condensate  dripping  may  be  troublesome  and 

may  cause  some  staining.  Avoid  windows  where 

steam may cause fogging or ice buildup.

 

 

5 −  Minimum clearance for horizontal vent termination 

from  any  door,  window,  gravity  air  inlet,  gas  or 

electric meter, regulators, and relief equipment is 

4 feet (1m) for United States installations.

 

 

In Canada, horizontal vent termination must have 

a  minimum  6-foot  horizontal  clearance  from  gas 

and electric meters and relief devices.

 

 

(INCLUDING ELBOWS)

 

 

Model

 

 

ft

 

m

 

 

   

 

HED−75

 

 

15

 

4.57

 

 

 

 

 

HED−100 THROUGH 300

 

 

N/A*

 

N/A*

 

 

 

 

 

 

*Not applicable for larger units. Maximum length of uninsulated vent 

is equal to maximum allowable vent length from table 2.

 

 

Refer  to  latest  editions  of  the  ANSI  Z223.1  or 

CSA−B149 for installation  compliance codes and 

with local authorities with jurisdiction.

 

 

6 −  Vent termination must be a minimum of 4 feet

 

(1.2m) horizontally from any soffit or under-eave 

vent.

 

 
 

7

Summary of Contents for HED Series

Page 1: ...mplate 17 Warranty 18 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exact ly could result in serious injury death or property damage Be sure to read and understand the installation operation and service instructions in this manual Improper installation adjustment alter ation service or maintenance can cause serious injury death or...

Page 2: ... in 31 5 16 32 3 16 41 1 8 3 11 16 40 17 1 2 3 1 4 25 39 1 8 15 3 8 35 1 16 9 HED 250 A S mm 795 817 1045 97 1016 445 83 635 994 391 891 229 HED 300 A S A Heat Exchanger Aluminum Steel S Heat Exchanger Stainless Steel Shipping The heater is completely assembled and is shipped with installation and operating instructions warranty certificate and flue transition Check the unit for shipping damage Th...

Page 3: ...e area clearance from the heater to combustible materials must be such that the combustible material must not attain a temperature above 160 F 71 C during continuous operation of the unit WARNING These units are CSA international design certified These duct heaters are certified for clearances to combustible material as listed in table 1 and on unit rating plate Accessibility and service clearance...

Page 4: ...onnection and not less than 2 equivalent diameters in length See figure 1 SINGLE BLOWER APPLICATION Top View 155 TRANSITION HED UNIT BLOWER AIR FLOW DUCT LENGTH L The formula for computing duct length L is 4WH W WidthH Height Inlet W H Duct length L is computed as shown by the formula and rounded to the nearest whole number MODEL INLET DUCT in mm DUCT NO WIDTH HEIGHT LENGTH L HED 75 15 13 3 8 29 3...

Page 5: ... rotate the combustion air inducer on HED models 200 250 and 300 Rotate the combustion air inducer assembly as follows 1 Remove the heater from the carton Decide the best duct heater orientation The vent can be installed in one of three discharge positions up left or right 2 If the inducer is to be rotated follow the instructions in this section otherwise refer to instructions under Venting sectio...

Page 6: ...l HED duct heaters are listed as Category 1 appliances for vertical vent installations 1 All HED duct heaters are to be used with NFPA or ANSI approved chimneys or U L listed type B 1 gas vents where applicable as well as the modifications and limitations listed in figure 2 Seal single wall vent material according to General Recommendations and Requirements section 2 Keep the vent connector runs a...

Page 7: ...ct heater If the HED duct heater is to be horizontally vented a positive pressure may be created in the vent The duct heater when installed with horizontal venting will perform as a category III appliance 1 Special vent materials approved for use with Category III appliances may be used with these units Refer to table 7 for venting components 2 If possible do not terminate the horizontal vent thro...

Page 8: ...he vent termination if permitted by authorities Fig 5 13 For horizontal venting the vent pipe must be supported with hangers no more than 3 feet 1m apart to prevent movement after installation 14 All horizontal vent applications which use Category III vent pipe must terminate with an approved Category III tee Opening end must face downward 15 When termination is routed through an exterior combusti...

Page 9: ...ructions OR listed special vent for Category III appliances SLOPE 1 4 IN PER FOOT RUN MAXIMUM NOTE Minimum horizontal length equals 5 feet 1 53 m This does not include termination tee Refer to table 6 for maximum length and number of elbows 12 INCHES 30 5 cm MINIMUM DOUBLE MALE VENT TERMINATION ADAPTER TEE Cat III kits only FIGURE 6 TABLE 5 Category III Horizontal Venting Components Required for H...

Page 10: ...fused disconnect switch with the fuse sized according to blower motor size Connect wiring through knockout on the junction box located on the side of the duct heater Refer to heater wiring diagram for connection information Use 18 gauge wire or larger for thermostat connections NOTE Electrically ground unit in accordance with local codes or in the absence of local codes in accordance with the curr...

Page 11: ...hese devices should be properly labeled by the installer GAS SUPPLY TO UNIT HEATER MANUAL MAIN SHUT OFF DISCONNECT GAS VALVE WILL NOT HOLD NORMAL TEST VALVE WHEN TEST PRESSURES OF 1 2 psig PRESSURES OF 1 2 psig 3 45kPa 3 45kPa OR HIGHER OR HIGHER WILL BE USED CAP UNIT HEATER FIGURE 8 Unit Start Up FOR YOUR SAFETY READ BEFORE LIGHTING WARNING Electric shock hazard Can cause injury or death Do not u...

Page 12: ...ttempt to light the burners manually 5 Honeywell VR8205 series turn manual knob on gas valve clockwise to OFF Do not force For White Rodgers 36 series gas valve move lever to OFF 6 Wait five minutes to clear out any gas If you then smell gas STOP Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you do not smell gas go to next step 7 Honeywell VR8...

Page 13: ...ximately centered in the tubes with no apparent impingement taking place 7 The ignition control will energize the ACC terminals approximately 45 seconds after ignition is established 8 After the thermostat demand is satisfied the gas valve is closed Five seconds after the demand is satisfied the combustion air inducer is shut off 9 The ignition control will de energize the ACC terminals approximat...

Page 14: ...e switch is factory set and no field adjustment is necessary Service LUBRICATION Combustion air inducer motor bearings are pre lubricated and sealed No further lubrication is necessary BURNERS 1 Periodically examine burner flames for proper appearance during the heating season 2 Before each heating season examine the burners for any deposits or blockage that may have occurred 3 Clean burners as fo...

Page 15: ...nit unit operating 3 Check amperage draw FLUE AND CHIMNEY Check all vent and vent connector joints for tightness Ensure that connections are sealed and that there are no blockages FAILURE TO OPERATE If unit fails to operate check the following 1 Is thermostat calling for heat 2 Is main disconnect closed 3 Is there a breaker tripped or a fuse blown 4 Is gas turned on at meter 5 Is manual shutoff va...

Page 16: ...l No Serial No Service Technician Electrical Connections Tight Air Shutters Properly Adjusted If Installed Supply Voltage Flue Connections Tight Blower Motor Lubrication O K Gas Piping Connections Tight Leak Tested THERMOSTAT Furnace Btu Input Calibrated Heat Anticipator Properly Set Line Pressure Manifold Pressure w c Level 16 ...

Page 17: ...TEMPLATE Location of Combustion Air Inducer Mounting Holes for Rotated Inducer EXISTING HOLE EXISTING HOLE EXISTING HOLE 17 ...

Page 18: ... credit in the amount of the heat exchanger original selling price toward the purchase of a new ADP unit heater No extended coverage granted for HED series heat exchangers For information on this product s warranty including accessing complete warranty terms registering for an extended warranty or obtaining instructions on filing a warranty claim please go to www ADPwarranty com In such states or ...

Page 19: ...19 ...

Page 20: ......

Reviews: