ADI LT boiler – Technical manual
Page
26
12. ELECTRIC DRAWINGS
The electric supply must be 220/230 V, 50 Hz, single phase, earth connection. The electric installation must
comply with the current rules. The electric power consumed by each boiler is indicated in the table of technical
characteristics.
(Remember: in case of 220/230 V, two phases, it is necessary to install an electric insulating transformer with
one of the phases of the secondary connected to earth acting as neutral).
Legend of the electric drawing:
1. Fuse
2. Contactor
3. Electric supply of the motor fan
4. Option: Boiler pump stop/start
(Consult: the use of separation relays depends on the programming of the control unit)
5. Probe / ionization electrode
6. Electric supply (220/230 V) of the multi-block gas valve
6b. Adaptor / connector only used in model ADI HT 105
7. Ignition transformer (220/230 V)
8. General switch: ON/OFF
9. Safety overheating thermostat
10. Display of reading
11. Signal of control of the modulation of the variable speed fan (PWM)
12. Air pressure switch
13. Minimum gas pressure switch
14. Electric supply: 220/230 V, 50 Hz, single phase with earth connection (main supply to the
boiler).
15. Stop/start switch external to the boiler: Stop/start external contact (open/close).
16. Signal of the boiler status: terminals with tension of 220/230 V, to be separated by means of a
relay.
17. Alarm indicator of boiler lockout: these are terminals with live tension of 220/230 V, to be
separated by means of a relay.
18. Water pressure sensor.
19. Return water temperature probe/sensor.
20. Flow water temperature probe/sensor.
23. Earth connection for burner
24. Option: Outside temperature probe (Consult: according to programming and installation)
25. Communication bus with additional modules “clip-in”. See the corresponding paragraphs.
26. Boiler control panel
27. Optional: electric supply of 220/230 V for additional modules “clip-in”
28. Boiler.