18.4.2 Change of fuel: from Propane gas to Natural gas, or vice versa
In order to change fuel (this operation must be carried out by an ADISA official service or by authorised professional
staff):
-
Reprogram the control unit
-
Adjust the boiler combustion with the new fuel to the correct parameters, either for Natural Gas or for Propane
Gas.
-
Characteristics plate: put the corresponding one according to the gas used.
The process is the same if you have to change from natural gas to propane.
Note: Propane option just available for models with power output lower than 550 kW.
Data for máximum power:
Model
Power
output
Power input
LPG Max
LPG Max
kW
kW
m
3
/h
kg/h
CD 70
70.5
72.7
3.0
6.0
CD 85
85
87.7
3.7
7.2
CD 105
104
107.2
4.5
8.8
CD 120
120
123.5
5.1
10.2
CD 175
161.8
166.0
6.9
13.7
CD 200
197.5
202.2
8.4
16.7
CD 250
241
246.5
10.3
20.4
CD 325
294
300.5
12.5
24.8
CD 375
354
361.2
15.1
29.8
CD 450
440
448.2
18.7
37.0
CD 550
530
546.4
22.8
45.1
LPG (Propane gas):
LCV: 23.98 kW/m
3
Density: 1.98 kg/m
3
Summary of Contents for ADI CD 375
Page 1: ...1 º º ADI CD CONDENSING BOILER TECHNICAL MANUAL OF INSTALLATION USE AND MAINTENANCE V 07 2017 ...
Page 7: ...ADI CD boiler Technical Manual 7 Models ADI CD 200 and higher A C D B J H G F E R S ...
Page 34: ...ADI CD boiler Technical Manual 34 12 1 Electric drawing ADI CD 70 750 ...
Page 35: ...ADI CD boiler Technical Manual 35 12 2 Electric drawing ADI CD 850 950 ...