ADI CD boiler - Technical Manual
43
14. DOMESTIC HOT WATER
If there is demand for DHW, the heat sources can be switched on at any time. The strategy is to produce the amount
of heat required at a certain point in time – and no more. For that purpose, switching programs, different setpoints and
release criteria are available.To activate the DHW, connect the storage tank sensor to B3 input (see the following
electric drawing) and select the DHW mode with the operating mode button
.
Off
Continuous operation, the setpoint being the DHW Frost Protection setpoint (5 °C).
On
DHW charging takes place automatically, the setpoint being the Nominal DHW setpoint or the Reduced DHW setpoint
according to the selected kind of DHW release.
Setpoints
0 10 20 30 40 50 60 70 80 90 100 °C
1612
1610
1614
74
71z
91
/0
91
0
a) System drawing: 1 Boiler and Domestic Hot Water