COMMISSIONING
Fig. 8
2
Add one or more ADICOS detectors to the query, e.g. using the autoscan feature.
Z
While the service PC is communicating with the detectors connected in the field, the red
LED (reply) as well as the yellow LED (query) should be flashing.
6.3.2 Integrating M-BUSMASTER XF via Optional LAN
Connection
The ADICOS M-BUSMASTER XF can be equipped with an Ethernet connection upon request.
The network card is based on a module XPort supplied by Lantronix. The MAC address of the
network card can be found on the label on the XPort.
1
2
xxx-xx-xxxxx-x-x
Fig. 9
1
MAC address
2
Ethernet cable
The Ethernet module automatically obtains its IP address from the DHCP server of the network.
Using the "Lantronix DeviceInstaller“ (https://www.lantronix.com/products/deviceinstaller/), a
software tool provided by the manufacturer of the XPort, the IP address of the respective MAC
address ADICOS M-BUSMASTER XF can be found or adapted as required.