COMMISSIONING
19
ADICOS M-BUSMASTER XF
420-2410-003 EN20
6
Click “Finish” and close the Device Installer.
Setting up M-Bus-Master in ADICOS Central Software
Prerequisite
Operation via auxiliary
module (Ethernet, etc.)
Verify that the jumper “A0” is plugged into the upper position
(Refer to Chap. “3.5.1 Jumper Settings “Interface””).
A0
A1
1
Adjust the interface parameters in the software as follows:
Fig. 15
Bus connection: Ethernet TCP/IP
TCP/IP setting: the preset or programmed IP address
Port: 10001
2
Click “OK” to confirm the settings.
3
Add ADICOS detectors to the query, e.g. using the autoscan feature.
Z
While the service PC is communicating with the connected detectors, the red LED (reply)
as well as the yellow LED (query) should be flashing.