The Start and End Triggers must be configured to control channels. End Trigger must drive channels to 0%.
Figure 10 - Start Trigger's Light Levels - Channels, not Outputs, must be controlled
for blink warning
Figure 11 - End Trigger's Light Levels - Channels, not Outputs, must be
controlled to 0% for blink warning
Timed override delay can be adjusted by changing the “Switch Timeout” setting of a switch in the Start Trigger.
The “Enable” setting must be selected, to gain access
to modify the “Switch Timeout”. Changing the “Switch
Timeout” of a switch device in the Start Trigger will
adjust the timed override delay of the schedule.
The following are “Switch Timeout”, or timed override
delay, options:
•
No Timeout – Sets the timed override delay to
0 min.
•
Default – Sets the timed override delay to 2
hrs.
•
# Minutes – Sets the timed override delay to
the selected minutes.
•
# Hours – Sets the timed override delay to the
selected hours.
Blink warning must be enabled