EN -
14
IT
EN
DE
FR
ES
RU
ACTUATECH S.p.A.
Via S. Lorenzo, 70, 25069 Villa Carcina (BS) Italy
Ph.
+39 030 8908142 •
Fax
+39 030 8908143 • [email protected] •
www.actuatech.com
Reference MAN81566 - 05/21
INSTRUCTION MANUAL
RP: RACK & PINION PART TURN PNEUMATIC ACTUATOR
RP10 - RP480
Spring Return (SR) Fail Open
Closed valve
Spring Return (SR) Fail Open
Opened valve
8. OPENING AND CLOSING ANGLE SETTING
RP actuators rotation angle is nominally 90° with a ± 5° adjusting stroke: closing setting from -5° to +5° and opening setting from 85°
to 95°. Before any operation, take the pressure off, disconnect air feeding and make sure that air ports have been completely vented.
A
B
A
B
GRANO
DADO
O-ring
RONDELLA
CAMMA
Adjusting screw nuts
Size
Thread Grub screw key Nut key
Torque (Nm)
RP 10
M6
ch.3
ch.10
10 - 11
RP 20
RP 40
RP 60
M8
ch.4
ch.13
22 - 25
RP 80
RP 120
RP 160
M10
ch.5
ch.16
38 - 43
RP 240
M12
ch.6
ch.18
85 - 90
RP 300
RP 480
M14
ch.6
ch.21
110 - 115
Rotazione oraria
dell'albero
Clockwise rotation
of the shaft
2
Rotazione antioraria
dell'albero
Counter-clockwise
rotation of the shaft
4