Installation and Commissioning Guide
Hercules Package Unit
45
Installation and Commissioning Guide - Hercules Package Unit
Doc. No.0525-021
Ver. 21 221110
NOTE
: To toggle (scroll)
Up
or
Down
from
existing menu, press
or
button.
Indoor Fan 1- 4: En/Disabled
Gfc37
Polling Time:
00.0 s
Outdoor Fan 1- 4: En/Disabled
Gfc38
Polling Time:
00.0 s
2
Gfc33
Room Temp/ Hum sensor fitted:
Yes/No
Use this temp sensor instead AI9:
Yes/No
(DIP Switch 1,6,7 ON)
2
Gfc34
Outside Temp/ Hum sensor fitted:
Yes/No
Use this temp sensor instead AI10:
Yes/No
(DIP Switch 6,7 ON)
Alarm disable
Gfc36
Probe9 / Probe12 sensor:
Yes/No
Constant Volume/HP & LP Trip:
Yes/No
VCD Earth Sensor
No
2
DeHum Setting
Gfc35
Heat / Cool Stage
Compressor start:
30.0%
Compressor stop:
20.0%
Enable Heat Reclaim: No
Gfc16
Setpoint SH / LowSH thresh.
Gfc19
LOP / MOP threshold
Supply Fan - In Heat
Gfc15
Limit time at start up in
heat mode / Heat Max. speed
Crankcase Heater On
Gfc13
Outside Temp. Set : °C
Delay Time :
1 m
Comp 1 / Comp 2 Enabled
Gfc32
Damper Scaling
Gfc29
Command Start / End
Output Start / End
2
Enable Heat Reclaim: Yes
Gfc16
- configured OK -
Max Check Time
Min (Supply-Room temp)
in Max Check Time
(Set-Room temp) to turn off mech heat
2
Heat Reclaim
Gfc18
Compensated Delta used
Reclaim D_Out: On / Off
Mech. Heat enable: On / Off
2
Turn off Heat reclaim
Gfc17
if Mech. heating is on?: NO / YES
2
VAV Mode:
Gfc14
Minimum Evaporating
Temperature : °C
Maximum Condensing
Temperature :
°C
Supply Volume PI Parameters
Gfc11
Proportional K / Integral Time
Return Temp. PI Parameters
Gfc12
Proportional K / Integral Time
Gf- 2
Gf- 1
Gfc
Gf- 2
Economy Cycle
Gfd2
Enabled:
No
d. Economy Setting
Gfd
Economy Cycle
Gfd2
Enabled:
Yes
Temperature Difference: °C
Outside Air Min Limit Temp: Yes/No
°C
2
Economy Cycle
Gfd3
Outside Air Max Limit
Temperature: Yes/No °C
Humidity: Yes/No
0.0% - 100%
Enthalpy: Yes/No
0.0 - 100.0kJ/kg
Moisture/Dew Point: Yes/No g/kg / c
Minimum Outside Air
Gfd1
Enable CO2:
No
Damper Position
20.0% - 99.9%
2
Economy Cycle
Gfd4
Enthalpy:
Yes/No
Difference:
0.0 - 100.0kJ/kg
Comp Oil Check
Gfc40
System 1 Not Ready - Enable: No / Yes
System 2 Not Ready - Enable: No / Yes
Cycle Duration: mins
Reset Oil Check: No
Comp Evac Mode
Gfc
41
System 1 Ready - Enable: No / Yes
System 2 Ready - Enable: No / Yes
Minimum Outside Air
Gfd1
Enable CO2:
Yes
CO2 Level
Damper Pos
ppm
%
Compressors
Gfc39
1st Stage Min Demand Start / Stop
2nd Stage Min Demand Start / Stop
2
CO2 Control
Gfc31
V12 Input:
4-20mH
Start:
0ppm
End:
2000ppm
Alarm Output:
Enabled
Sensor Fault: < 50ppm
>1950ppm