Installation and Commissioning Guide
Split Ducted Indoor Units
Installation and Commissioning Guide - Split Ducted Indoor Unit
Doc. No.0525-074
Ver. 3 200811
9
04.04. EVA170S
DUCT WORK
DUCT WORK
850 MM
SERVICE
CLEARANCE
850 MM
SERVICE
CLEARANCE
(ELECTRICALS)
EC
ID FAN
EC
ID FAN
INDOOR COIL
HEIGHT CLEARANCE = 410MM
MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES
OVERALL NOMINAL DIMENSION (H X W X L)
= 412 X 1290 X 615
SUPPLY DUCT (H X W) = 300 X 715
RETURN DUCT = 340 X 1100
CONDENSATE DRAIN CONNECTION
= 20MM OD
UNIT MODEL NUMBER
UNIT WEIGHT
(kg)
EVA150S
56
1100
80
715
20
20
INDOOR COIL
412
O/A
615 O/A
1252
40
300
72
40
340
22
50
115
248.5
248.5
575
SUPPLY
AIR
RETURN
AIR
1290 O/A
40
535
65
47
EC
INDOOR
FAN
EC
INDOOR
FAN
SUPPLY AIR
TOP VIEW
FRONT VIEW
SIDE VIEW
NOTES:
1. Do not scale drawing. All dimensions are
in mm unless specified.
2. Service Clearances given are suggested
minimum based on the condition that
the spaces around the units are free
from any obstructions and a walkway
passage of 1000mm between the units
or between the unit and the outside
perimeter is available.
3. Minimum service access clearances are
responsibilities of the installer, ActronAir
will not be held liable for any extra
charges incurred due to lack of access.
THIRD ANGLE
PROJECTION