Installation and Commissioning Guide
Split Ducted Indoor Units
Installation and Commissioning Guide - Split Ducted Indoor Unit
Doc. No.0525-074
Ver. 3 200811
13
NOTES:
1. Do not scale drawing. All dimensions are
in mm unless specified.
2. Service Clearances given are suggested
minimum based on the condition that
the spaces around the units are free
from any obstructions and a walkway
passage of 1000mm between the units
or between the unit and the outside
perimeter is available.
3. Minimum service access clearances are
responsibilities of the installer, ActronAir
will not be held liable for any extra
charges incurred due to lack of access.
THIRD ANGLE
PROJECTION
DUCT WORK
TO FAN SECTION
(0M MIN - 6M MAX)
850 MM
SERVICE
CLEARANCE
TOP VIEW
COIL SECTION
DUCT WORK
HEIGHT CLEARANCE = 340mm
MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES
850 MM
SERVICE
CLEARANCE
20
1212
20
176
900
176
51
345
410 O/A
131
156
43
25
31
1190
(MTG C-C DIST)
31
342 O/A
302
94
29
15
23
81
22
199
283
131
81
22 283
345
51
176
900
176
SAFETY DRAIN
Ø 20mm ID
PRIMARY DRAIN
Ø 20mm OD
COIL SENSOR HOLE
Ø 35mm
1252 O/A
31
GAS PIPE
Ø 19.05mm (3/4")
SWAGED
LIQUID PIPE
Ø 9.52mm (3/8")
SWAGED
TOP VIEW
FRONT VIEW - SUPPLY AIR
REAR VIEW - RETURN AIR
EAA150S / EAA170S
OVERALL NOMINAL DIMENSION (H X W X L)
= 410 X 1252 X 342
SUPPLY DUCT (H X W) = 345 X 900
RETURN DUCT = 345 X 900
UNIT MODEL NUMBER
UNIT WEIGHT
(kg)
EAA150S
27
EAA170S
29
SIDE VIEW