TC110 Series
Water Temperature Control Units 882.03888.00
•
09/19/2018
16
Chapter 3:
Installation
3-1
Installation Location Considerations
TC110 Series systems are portable and can be installed almost anywhere. As with all
equipment installations, follow all applicable codes and regulations.
The recommended ambient temperature range for TC110 Series installations is from
32°F (0°C) to a maximum operating ambient temperature of 131°F (55°C).
Recommended ambient storage temperature range is from -13°F to 149°F (-25°C to
65°C). If storing the unit below freezing temperatures, make sure the unit has an
antifreeze mixture circulated inside.
Provide a minimum of twelve inches (12” or about 30 cm) clearance on all sides of
the cabinet to allow circulation of cooling air.
Locate the unit as close to the process as is practical.
3-2
Process Approach Temperature Considerations
If the differential (
) between COOLING WATER IN and TO PROCESS temperatures is less
than 10°F (5.5°C), consult our Sales Department for advice on how to control low approach
applications.
3-3
External Piping Sizing Considerations
All external hose and piping should be adequately sized to assure minimum external
pressure drop.
Low external piping pressure drop is needed for best operation.
Use a backup wrench to support TC110 Series system piping when making process
piping connections.
All external valves, fittings, and hoses must be rated at a minimum of
150 psig and 250°F (1034 kPa/10.3 bar and 121°C).