Adjusting the Pressure Switch
The pressure switch used in your TC110 Series water temperature control unit is factory set
at 16 psig (110 kPa/1.1 bar). However, if the process does not require the unit to operate at
250°F (121°C), you can adjust the switch to meet your process needs.
Tools Required
Small flat blade screwdriver
#2 Phillips head screwdriver
HAZARDOUS ELECTRICAL CURRENT PRESENT.
Maintain a safe ground and disconnect the power supply
before servicing the unit.
Make sure a qualified electrician makes electrical connections;
disconnect/lock out electricity using OSHA 20CFR 1910.147
standards when servicing the unit.
To adjust the pressure switch:
Using a small, flat-blade screwdriver, carefully remove the plug
at the top of the switch.