TC110 Series
Water Temperature Control Units 882.03888.00
•
09/19/2018
31
Important!
Do not change any of the control settings without
consulting the ACS Group Service Department.
The ACS Group warranty does not cover temperature control unit failures
from tampering with controller settings!
Down Key
Each press of the Down Arrow key decrements or reduces the values or settings on the
SV Set Value display.
Up Key
Each press of the Up Arrow key increments or advances the values or settings on the SV
Set Value display.
4-8
Checking Motor Rotation Direction
Check for correct pump rotation direction by looking at the end of the motor. Press the
ON/OFF switch from the OFF ( O ) position to the ON ( | ) button, and note the direction
that the motor turns. Rotation should be clockwise when viewed from the motor end.
Make sure that a qualified electrician performs the following steps.
To change rotation direction:
Disconnect and lock out power at the fused disconnect.
Reverse any two incoming leads at the power terminal blocks.
Do not switch leads at the motor or motor starters.