Menu group Function
Input
Description
SEr
Service – includes all parameters concerning service purposes
t_F
Input of the system damping for reassuring of cyclic fluctuating temperature signals.
The adjustment range is 0...40 seconds, in steps of 0,1 seconds
ErrN
noE
No error recorded in the error memory.
brch
A wire break at the internal connections of the sensor element has been detected.
Hur
A short circuit at the internal connections of the sensor element has been detected
FLAS
An error in the internal nonvolatile data memory (flash) has been detected.
Nunt
The lower measuring range limit value (display zero) has been underrun.
NuEb
The upper measuring range limit value (display span) has been exceeded.
Aunt
The lower limit value of the current output (3,9mA) has been underrun.
AuEb
The upper limit value of the current output (21mA) has been exceeded.
S1oG
The switch back point rSP1 of the switch output 1 has been adjusted higher or equal to the
switch point SP_1.
S2oG
The switch back point rSP2 of the switch output 2 has been adjusted higher or equal to the
switch point SP_2.
S1oP
The switch output 1 is not activated, although it should be.
S2oP
The switch output 2 is not activated, although it should be.
rAN
An error in the internal working memory (RAM) has been detected.
drFt
The exceedance of the set drift threshold value has been detected.
NA
Maximum value memory – display of the highest measured temperature value.
Nin
Minimum value memory – display of the lowest measured temperature value.
drAL
A drift alarm is only made, if the set drift threshold value, the difference between the
temperature measuring values of the two sensor elements, has been exceeded.
The adjustment range is 0,2...5 K, in steps of 0,1K.
drd
A drift alarm is only made, if after the exceedance of the drift threshold value and after the set
drift delay time the drift threshold value has been already exceeded.
By this, e.g. the different response time of the two sensor elements at temperature deviations
can be compensated.
The adjustment range is 0...300 seconds, in steps of 1 second.
drb
AUS
The redundancy function is deactivated
Ein
The redundancy function is activated. At the failure of the sensor element Pt100 the measuring
is continued with the semiconductor sensor element.
301
Version number of the installed firmware
FrES
Factory Reset – reset of all parameters to factory values
SPEi
Storage – loss protected storage of all parameters
Menu group Function
Input
Description
Switch point menu
SP_1
The current switch point / upper switch point of switch output 1is shown in the display and can
be adjusted by the control keys +/- and >.
rSP1
The current switch back point / lower switch point of switch output 1 is shown in the display
and can be adjusted by the control keys +/- and >.
SP_2
The current switch point / upper switch point of switch output 2 is shown in the display and can
be adjusted by the control keys +/- and >.
rSP2
The current switch back point / lower switch point of switch output 2 is shown in the display
and can be adjusted by the control keys +/- and >.
Fc_1
The set switch function of the switch output 1 is displayed. This setting cannot be changed
here.
HFno
The switch output 1 operates in hysteresis function with working principle normal open
HFnc
The switch output 1 operates in hysteresis function with working principle normal closed
FFno
The switch output 1 operates in window function with working principle normal open
FFnc
The switch output 1 operates in window function with working principle normal closed
Fc_2
The set switch function of the switch output 2 is displayed. This setting cannot be changed
here.
HFno
The switch output 2 operates in hysteresis function with working principle normal open
HFnc
The switch output 2 operates in hysteresis function with working principle normal closed
FFno
The switch output 2 operates in window function with working principle normal open
FFnc
The switch output 2 operates in window function with working principle normal closed