ACS-CONTROL-SYSTEM GmbH
l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
24
Characteristic deviation
3) 5) 8)
Display / Switch output
≤ ±(0,4K + 0,002 * [t])
[t] = process temperature in °C, no sign, unit K
≤ ±0,6% FS
2)
Current output
≤ ±(characteristic dev. display / switch 0,1% FS
2)
)
≤ ±0,9Kat ±100°C / meas. range –99,9..+200°C / TD
7)
=1
Characteristic deviation
3) 5) 8)
Type self-supervision
Display / Switch output
≤ ±0,2K
Current output
≤ ±0,4K
Drift monitoring
≤ ±0,2K
Repeatability
6) 8)
≤ ±0,1% FS
2)
Influence of supply voltage
≤ ±0,002% FS
2)
/ V
Long term drift
6) 8)
≤ ±0,1% FS
2)
/ year
Temperature deviation
6) 8)
Display / Switch output
≤ ±0,003% FS
2)
/ K
Current output
≤ ±0,008% FS
2)
/ K
Response time
9)
t90 ≤10s sensor tube tip diameter 6mm
t90 ≤14s sensor tube tip diameter 8mm
t90 ≤17s sensor tube tip diameter 10mm
2)
Referring to nominal measuring span resp. full scale (FS)
5)
Limit value adjustment acc. to EN/IEC 60770-1
6)
Specification for TD
7)
= 1 (adjusted measuring range = nominal measuring range).
Specification for TD
7)
≥ 1 (adjusted measuring range ≤ nominal measuring range) = specification at nominal measuring range x TD
7)
7)
Turn-Down TD = nominal measuring range (FS
2)
) / adjusted measuring range)
8)
At reference conditions
9)
Acc. to DIN EN 60751 / water / 0,4 m/s / temperature step 23 to 33°C
7.4
Process conditions
Process temperature
The permitted range results from the
narrowest limitation of standard range
resp. extended range.
Measuring range type 2
-99,9°C…+200°C, max. -103°C…230°C
Measuring range type 3
-99,9°C…+500°C, max. -130°C…530°C
Measuring range type 4
-50°C…+175°C, max. -55°C…+180°C
Limitation
Gasket - FPM -25°C...+200°C
Gasket - EPDM -40°C...+140°C
Process pressure
Process connection type 0
≤ 20 bar (compression fitting V4A)
0 bar (compression fitting PTFE)
Process connection type 1 / type 3
≤ 100 bar
Process connection type 4 / type 5
≤ 50 bar
Summary of Contents for Thermocont TS4S