Menu group Function
Input
Description
SP2
Switch output 2 – includes all parameters concerning the switch output 2
SP_2
NSiG
Adjustment with applied signal – The actual applied temperature value is captured as switch
point resp. upper switch point
oSiG
Adjustment without applied signal – The actual switch point / upper switch point is shown in
the display and can now be adjusted by the operation keys +/- and >.
rSP2
NSiG
Adjustment with applied signal – The actual applied temperature value is captured as switch
back point resp. lower switch point
oSig
Adjustment without applied signal – The actual switch back point / lower switch point is shown
in the display and can now be adjusted by the operation keys +/- and >.
Fc_2
HF_2
The switch output 2 operates in hysteresis function with switch point and switch back point
FF_2
The switch output 2 operates in window function with lower and upper switch point
nonc
no
The switch output 2 operates in open-circuit principle resp. – no normally open
nc
The switch output 2 operates in closed-circuit principle resp. – nc normally closed
dSP2
Switch delay time for switch point / upper switch point of switching output 2.
The switch output 2 is only activated, if after the entrance of the switch condition and after the
set switch delay time the temperature signal already fulfills the switch conditions. By this e.g.
temperature fluctuations can be eliminated.
The adjustment range is 0...99 seconds, in steps of 0,1 seconds
drP2
Switch delay time for switch back point / lower switch point of switching output 2.
The switch output 2 is only activated, if after the entrance of the switch back condition
and after the set switch delay time the temperature signal already fulfills the switch back
conditions. By this e.g. temperature fluctuations can be eliminated.
The adjustment range is 0...99 seconds, in steps of 0,1 seconds
SiN2
AuS2
Simulation – the switch output 2 is deactivated
Ein2
Simulation – the switch output 2 is activated
Menu group
Function
Input
Description
AbGL
Adjustment – includes all parameters concerning the temperature adjustment
2Ero
NSiG
Adjustment lower temperature reference value with applied signal
- The actual applied temperature value is captured as lower temperature reference value.
- The output current of 4mA, that can be adjusted by the control keys +/- and > arbitrarily, is
assigned to this temperature reference value. Adjustment range 3,9mA to 21mA.
- If the adjusted measuring range is lower than 25% of the nominal measuring range, the
change will be refused and the display shows EEEE.
- An already set offset will be regarded at the adjustment.
oSiG
Adjustment lower temperature reference value without applied signal
- The freely adjustable pressure value, in the set unit - Unit-, is captured as lower temperature
reference value.
- The lower output current end value, 4mA, refers to this pressure reference value.
- The measuring span cannot be adjusted lower than 25% of the nominal measuring range.
- An already set offset will be regarded at the adjustment.
SpAn
NSiG
Adjustment upper temperature reference value with applied signal
- The actual applied temperature value is captured as upper temperature reference value.
- The output current of 20mA, that can be adjusted by the control keys +/- and > arbitrarily, is
assigned to this temperature reference value. Adjustment range 3,9mA to 21mA.
- If the adjusted measuring range is lower than 25% of the nominal measuring range, the
change will be refused and the display shows EEEE.
- An already set offset will be regarded at the adjustment.
oSiG
Adjustment upper pressure reference value without applied signal
- The freely adjustable pressure value, in the set unit - Unit-, is captured as upper pressure
reference value.
- The upper output current end value, 20mA, refers to this pressure reference value.
- The measuring span cannot be adjusted lower than 25% of the nominal measuring range.
- An already set offset will be regarded at the adjustment.
oFFS
The temperature measuring value can be shift by an offset of up to 25°C.
This can be necessary in unfavorable installation situations or at considerable temperature
differences between medium and measurement position.
inS
AUSA
The output current corresponds to the assignment of the adjustment >> 4...20mA
EinA
The output current behaves inverted to the assignment of the adjustment >> 20...4mA
SiNA
The current output can be arbitrarily simulated in the whole utilizable range from 3,8mA to
22mA by using the operation keys +/- and >.
ErrS
oFF
The current output operates linear in the range from 3,9mA to 21,0mA. A current output
besides this limits is not possible, the end values are kept at exceedance. An error current
output at underrun resp. exceedance does not occur.
FS38
The current output operates linear in the range from 4,0mA to 20,0mA. At underrun of 4mA
resp. at exceedance of 20mA a constant current of 3,8mA is generated.
FS22
The current output operates linear in the range from 4,0mA to 20,0mA. At underrun of 4mA
resp. at exceedance of 20mA a constant current of 22mA is generated.