1
with current and voltage input signals, scaling is required (see chapter 5.3)
Configuration level
Operating manual MIR-491
25
Configuration parameters
Name
Value range Description
Default
23
KTY 11-6 (special 0...4500 Ohm)
24
special 0...450 Ohm
30
0...20mA / 4...20mA
1
40
0...10V / 2...10V
1
41
special 0...100 mV
1
50
potentiometer 0...160 Ohm
51
potentiometer 0...450 Ohm
52
potentiometer 0...1600 Ohm
53
potentiometer 0...4500 Ohm
S.Lin
Linearization (only at
S.tYP
= 23 (KTY 11-6), 24
(0...450 W), 30 (0..20mA), 40 (0..10V) and 41 (0...100mV) )
0
0
none
1
Linearization to specification. Creation of linearization table
with BlueControl (engineering tool) possible. The
characteristic for KTY 11-6 temperature sensors is preset.
Corr
Measured value correction / scaling
0
0
Without scaling
1
Offset correction (at
CAL
level)
2
2-point correction (at
CAL
level)
3
Scaling (at
PArA
level)
fAI1
Forcing INP1
(only visible with BlueControl!)
0
0
No forcing
1
Forcing via serial interface
InP.2
Name
Value range Description
Default
I.Fnc
Function selection of INP2
1
0
no function (subsequent input data are skipped)
1
heating current input
2
external set-point (
SP.E
)
3
Yp input
4
Second process value X2
5
Y.E
input
6
no controller input (e.g. transmitter input instead)
S.tYP
Sensor type selection
30
30
0...20mA / 4...20mA
1
31
0...50mA AC
1
50
Potentiometer ( 0...160 Ohm)