![ACS contsys MIR-491 Operating Manual Download Page 37](http://html1.mh-extra.com/html/acs-contsys/mir-491/mir-491_operating-manual_3046907037.webp)
Configuration level
Operating manual MIR-491
37
Configuration parameters
Name
Value range Description
Default
di.Fn
Function of digital inputs (valid for all inputs)
0
0
direct
1
inverse
2
toggle key function
fDI1
Forcing di1
(only visible with BlueControl!)
0
0
No forcing
1
Forcing via serial interface
fDI2
Forcing di2
(only visible with BlueControl!)
0
0
No forcing
1
Forcing via serial interface
fDI3
Forcing di3
(only visible with BlueControl!)
0
0
No forcing
1
Forcing via serial interface
othr
Name
Value range Description
Default
bAud
Baudrate of the interface (only visible with OPTION)
2
0
2400 Baud
1
4800 Baud
2
9600 Baud
3
19200 Baud
Addr
1...247
Address on the interace (only visible with OPTION)
1
PrtY
Data parity on the interface (only visible with OPTION)
1
0
no parity (2 stop bits)
1
even parity
2
odd parity
dELY
0...200
Delay of response signal [ms] (only visible with OPTION)
0
Unit
Unit
1
0
without unit
1
°C
2
°F
dP
Decimal point (max. number of digits behind the decimal
point)
0
0
no digit behind the decimal point
1
1 digit behind the decimal point
2
2 digits behind the decimal point
3